      <title-group><article-title>Smoke exhaust experiments in an atrium model</article-title></title-group>
    <contrib-group>
      <contrib contrib-type="author">
        <name><surname>Liu</surname><given-names>Fang</given-names></name>
        <xref ref-type="aff" rid="aff1"/>
      </contrib>
      <contrib contrib-type="author">
        <name><surname>Fu</surname><given-names>Xiangzhao</given-names></name>
        <xref ref-type="aff" rid="aff1"/>
      </contrib>
      <contrib contrib-type="author">
        <name><surname>Lin</surname><given-names>Zhengguo</given-names></name>
        <xref ref-type="aff" rid="aff1"/>
      </contrib>
      <aff id="aff1">Faculty of Urban Construction and Environment, Chongqing University, Chongqing 400044, P.R. China</aff>
    </contrib-group>
      <pub-date publication-format="electronic" date-type="pub"><day>24</day><month>10</month><year>2003</year></pub-date>
      <volume>2</volume>
      <issue>1</issue>
      <isbn publication-format="electronic">978-1-995850-10-8</isbn>
      <fpage>301</fpage>
      <lpage>304</lpage>
      <self-uri xlink:href="https://caravelpress.com/proceedings/set/papers/2003.067"/>
      <permissions>
        <copyright-statement>© 2003 Copyright WSSET</copyright-statement>
        <copyright-year>2003</copyright-year>
      </permissions>
      <abstract><p>A series of experiments under various smoke control conditions during an atrium fire were conducted in a reduced-scale compartment that was constructed to be a 1/8-scale modeling of the PolyU/USTC Atrium. The steady-state fire experiments were conducted and the distributions of temperature and smoke visibility were measured. The result indicates that the smoke exhaust rate, exhaust inlet location, fire source power and the lower region pressurization can impact the effectiveness of the exhaust systems. As expected, the descent of the smoke layer can be reduced with the increase of smoke exhaust rate. It also can be found that the exhaust system, which the exhaust inlets were located equably under the smoke layer, is effective in extracting gases from hot layer. The lower region pressurization experiments demonstrated that this method is an effective smoke control method. This will be contributed to the fact that the exhaust system needs the air supply from the lower of the space to replace the air flowing out of the vents. More comprehensive studies on exhaust inlet location, exhaust rate, makeup air inlet location and air supply rate are needed.</p></abstract>
      <kwd-group kwd-group-type="author">
        <kwd>Atrium building</kwd>
        <kwd>fire</kwd>
        <kwd>smoke control</kwd>
      </kwd-group>
      <conference>
        <conf-date>24 to 27 October 2003</conf-date>
        <conf-name>2nd International Conference on Sustainable Energy Technologies</conf-name>
        <conf-acronym>SET2003</conf-acronym>
        <conf-num>2</conf-num>
        <conf-loc>Chongqing, China</conf-loc>
      </conference>
    </article-meta>
  </front>
  <body>
  </body>
  <back>
    <ref-list>
      <ref id="ref-r1">
        <mixed-citation publication-type="journal">NFPA 92B, Guide for smoke management system in malls, atria and large area. Quincy, Mass.: National Fire Protection Association, 1995.</mixed-citation>
      </ref>
      <ref id="ref-r2">
        <mixed-citation publication-type="journal">Hansell G.O.&amp; Morgan H.P.(1994) Design approaches for smoke control in atrium buildings. Building Research Establishment, BRE report No.256</mixed-citation>
      </ref>
      <ref id="ref-r3">
        <mixed-citation publication-type="journal">Liu F. , Yan Z. J. Current Situation and Prospects of Atrium Smoke Management Research. Journal of Chongqing Jianzhu University Vol. 21 No.6, pp.113-118 (1999)</mixed-citation>
      </ref>
      <ref id="ref-r4">
        <mixed-citation publication-type="journal">Chow W. K. , Simulation of the Atrium Fire Environment in Hong Kong. ASHRAE Transactions, Vol. 99 No.2, pp.163-168 (1993)</mixed-citation>
      </ref>
      <ref id="ref-r5">
        <mixed-citation publication-type="journal">Li Y. Z., Huo R., Yuan L. M., Li P. D., Fan W. C., Study of Smoke Filling Processes in an Atrium. Journal of China University of Science and Technology Vol. 29No.5, pp.590-594 (1999)</mixed-citation>
      </ref>
      <ref id="ref-r6">
        <mixed-citation publication-type="journal">Cooper L. Harkleroad Y., M., Rinkinen W., An Experimental Study of Upper Hot Layer Stratification in Full-Scale Multi-room Fire Scenarios. Journal Of Heat Transfer, Vol.104, pp.741-749 (1982)</mixed-citation>
      </ref>
      <ref id="ref-r7">
        <mixed-citation publication-type="journal">Klote J. H., New Developments in Atrium Smoke Management. ASHRAE Transactions, Vol. 106 No.2, pp.620-626 (2000)</mixed-citation>
      </ref>
      <ref id="ref-r8">
        <mixed-citation publication-type="journal">Klote J. H., Prediction of Smoke Movement in Atria: Part II---Application to Smoke Management. ASHRAE Transactions, Vol.103 No.2, pp.545-553 (1997)</mixed-citation>
      </ref>
    </ref-list>
  </back>
</article>