<?xml version="1.0" encoding="UTF-8"?>
<!DOCTYPE article PUBLIC "-//NLM//DTD JATS (Z39.96) Journal Publishing DTD v1.3 20210610//EN" "JATS-journalpublishing1-3.dtd">
<article xmlns:xlink="http://www.w3.org/1999/xlink" xmlns:mml="http://www.w3.org/1998/Math/MathML" dtd-version="1.3" article-type="research-article" xml:lang="en">
  <front>
    <journal-meta>
      <journal-title-group><journal-title>SET Proceedings</journal-title></journal-title-group>
      <issn pub-type="epub">2978-4387</issn>
      <publisher><publisher-name>Caravel Press</publisher-name></publisher>
    </journal-meta>
    <article-meta>
      <article-id pub-id-type="doi">10.65582/set.2004.081</article-id>
      <article-id pub-id-type="publisher-id">2004.081</article-id>
      <title-group><article-title>Performance Testing of a Condensing Modified Air Conditioner Using the Ground as a Heat Sink</article-title></title-group>
    <contrib-group>
      <contrib contrib-type="author">
        <name><surname>Permchart</surname><given-names>W.</given-names></name>
        <xref ref-type="aff" rid="aff1"/>
      </contrib>
      <contrib contrib-type="author">
        <name><surname>Khedari</surname><given-names>J.</given-names></name>
        <xref ref-type="aff" rid="aff2"/>
      </contrib>
      <contrib contrib-type="author">
        <name><surname>Tanatvanit</surname><given-names>S.</given-names></name>
        <xref ref-type="aff" rid="aff3"/>
      </contrib>
      <aff id="aff1">Department of Agricultural Engineering, Faculty of Engineering, King Mongkut’s Institute of Technology Ladkrabang, Bangkok 10520, Thailand</aff>
      <aff id="aff2">School of Energy and Materials, King Mongkut’s University of Technology Thonburi Bangkok 10140, Thailand</aff>
      <aff id="aff3">Environmental Science Program, Faculty of Science Ramkhamhaeng University, Bangkok 10240, Thailand</aff>
    </contrib-group>
      <pub-date publication-format="electronic" date-type="pub"><day>28</day><month>06</month><year>2004</year></pub-date>
      <volume>3</volume>
      <isbn publication-format="electronic">978-1-995850-06-1</isbn>
      <fpage>1</fpage>
      <lpage>4</lpage>
      <self-uri xlink:href="https://caravelpress.com/proceedings/set/papers/2004.081"/>
      <history>
        <date date-type="received"><string-date>28 June 2004</string-date></date>
      </history>
      <permissions>
        <copyright-statement>© 2004 Copyright WSSET</copyright-statement>
        <copyright-year>2004</copyright-year>
      </permissions>
      <abstract><p>This paper presents the results of the experimental tests of the cooling performance of a 3.5-kW condensing modified air conditioner (referred to as the CM-AC) by using the ground as a heat sink of a condensing unit. In the tests, not only the cooling capacity of the CM-AC with an optimal length of a condensing coil but also the life expectancy of this copper coil buried underground at 1 m depth have been investigated. The lengths of copper coils fabricated and used as condensing units of the CM-AC were set at 67, 50, 40 and 30 m whereas that of a 3.5-kW conventional split-type air conditioner (referred to as the C-AC) was about 22 m. R-134a was used as the refrigerant of both types of air conditioners. The results have shown that the ground has the potential to absorb the heat rejected from a condenser of the CM-AC. The coefficient of performance (COP) of the C-AC was about 2.5 whereas those of the CM-AC were found to be higher values except the case of 30-m-long condensing coil. It was found that the COPs of the CM-AC with condensing coils of 67, 50 and 40 m long were about 6.9, 5.5 and 3.3 respectively while that of 30-m-long one was about 2.1. The electrical consumptions of the CM-AC were found lower than that of the C-AC, on average, 11-15%. In addition, the ground temperatures near the buried copper coil had been increased insignificantly during the tests (&lt; 1.5°C). Moreover, it was found that the underground condensing coil of the CM-AC can be used as a condenser without any damages for more than 5 years.</p></abstract>
      <kwd-group kwd-group-type="author">
        <kwd>air conditioner</kwd>
        <kwd>condenser</kwd>
        <kwd>ground</kwd>
      </kwd-group>
      <conference>
        <conf-date>28 to 30 June 2004</conf-date>