<?xml version="1.0" encoding="UTF-8"?>
<!DOCTYPE article PUBLIC "-//NLM//DTD JATS (Z39.96) Journal Publishing DTD v1.3 20210610//EN" "JATS-journalpublishing1-3.dtd">
<article xmlns:xlink="http://www.w3.org/1999/xlink" xmlns:mml="http://www.w3.org/1998/Math/MathML" dtd-version="1.3" article-type="research-article" xml:lang="en">
  <front>
    <journal-meta>
      <journal-title-group><journal-title>SET Proceedings</journal-title></journal-title-group>
      <issn pub-type="epub">2978-4387</issn>
      <publisher><publisher-name>Caravel Press</publisher-name></publisher>
    </journal-meta>
    <article-meta>
      <article-id pub-id-type="doi">10.65582/set.2005.042</article-id>
      <article-id pub-id-type="publisher-id">2005.042</article-id>
      <title-group><article-title>Energy-conservation and Optimization Study of SPF Laboratory Animal Room Air System in Air Conditioning —Discussion on the Best Air Change Rates</article-title></title-group>
    <contrib-group>
      <contrib contrib-type="author">
        <name><surname>Jiang</surname><given-names>Xinbo</given-names></name>
        <xref ref-type="aff" rid="aff1"/>
      </contrib>
      <contrib contrib-type="author">
        <name><surname>Liu</surname><given-names>Zehua</given-names></name>
        <xref ref-type="aff" rid="aff2"/>
      </contrib>
      <contrib contrib-type="author">
        <name><surname>Liu</surname><given-names>Yuanquan</given-names></name>
        <xref ref-type="aff" rid="aff2"/>
      </contrib>
      <aff id="aff1">Design &amp; Art school of Nanhua University, Hengyang, China</aff>
      <aff id="aff2">Architecture resource &amp; environment engineering school of Nanhua University, Hengyang, China</aff>
    </contrib-group>
      <pub-date publication-format="electronic" date-type="pub"><day>23</day><month>09</month><year>2005</year></pub-date>
      <volume>4</volume>
      <issue>1</issue>
      <isbn publication-format="electronic">978-7-112-07718-2</isbn>
      <fpage>187</fpage>
      <lpage>191</lpage>
      <self-uri xlink:href="https://caravelpress.com/proceedings/set/papers/2005.042"/>
      <history>
        <date date-type="received"><string-date>23 September 2005</string-date></date>
      </history>
      <permissions>
        <copyright-statement>© 2005 Copyright WSSET</copyright-statement>
        <copyright-year>2005</copyright-year>
      </permissions>
      <abstract><p>This paper simulated and analyzed the concrete project of laboratory animal room by CFD software, studies the best air change rate in laboratory room, and analyzed the energy-conservation potential of the air system of air conditioning. the studies indicated the best air changes of laboratory animal room is 14 times/h which take the air distribution of supplying in ceiling diffuser and exhausting air in underside. compare air change rates of 20 times/h which taken in old system, The 30% energy of the air system of the air conditioning can be saved.</p></abstract>
      <kwd-group kwd-group-type="author">
        <kwd>Energy-conservation</kwd>
        <kwd>Laboratory Animal Room</kwd>
        <kwd>the Best Air Change Rates</kwd>
      </kwd-group>
      <conference>
        <conf-date>23 to 25 September 2005</conf-date>
        <conf-name>4th International Conference on Sustainable Energy Technologies</conf-name>
        <conf-acronym>SET2005</conf-acronym>
        <conf-num>4</conf-num>
        <conf-loc>Jinan, China</conf-loc>
      </conference>
    </article-meta>
  </front>
  <body>
  </body>
  <back>
    <ref-list>
      <ref id="ref-r1">
        <mixed-citation publication-type="journal">Ze-hua Liu, Xin-bo Jiang: 2004, The Simulation and analysis of SPF laboratory animal room air distribution and airborne pollutant distribution. The 2nd international conference on built environment and public health, pp333~340</mixed-citation>
      </ref>
      <ref id="ref-r2">
        <mixed-citation publication-type="journal">Wu DY, Joiner GN, McFarland AR: 1985, A forced-air ventilation system for rodent cages. Lab Anim Sci. Oct，35(5)：499～504.</mixed-citation>
      </ref>
      <ref id="ref-r3">
        <mixed-citation publication-type="journal">Yoshida K, Okamoto M, Tajima M, Kurosawa T: 1995, Invention of a forced-air-ventilated micro-isolation cage and rack system-environment within cages: temperature and ammonia concentration，Exp Anim. 43(5)：703～713.</mixed-citation>
      </ref>
      <ref id="ref-r4">
        <mixed-citation publication-type="journal">Yoshida K, Okamoto M, Tajima M, Kurosawa T : 1997, Intra-cage air change rate on forced-air-ventilated micro-isolation system-environment within cages: carbon dioxide and oxygen concentration. Exp Anim. 46(4)：251～258</mixed-citation>
      </ref>
      <ref id="ref-r5">
        <mixed-citation publication-type="journal">Fujita S, Obara T, Tanaka I, Yamauchi C: 1981, Distribution of environmental temperature and relative humidity according to the number of conditioned air changes in laboratory animals rooms，Jikken Dobutsu. 30(1)：21～30.</mixed-citation>
      </ref>
    </ref-list>
  </back>
</article>