<?xml version="1.0" encoding="UTF-8"?>
<!DOCTYPE article PUBLIC "-//NLM//DTD JATS (Z39.96) Journal Publishing DTD v1.3 20210610//EN" "JATS-journalpublishing1-3.dtd">
<article xmlns:xlink="http://www.w3.org/1999/xlink" xmlns:mml="http://www.w3.org/1998/Math/MathML" dtd-version="1.3" article-type="research-article" xml:lang="en">
  <front>
    <journal-meta>
      <journal-title-group><journal-title>SET Proceedings</journal-title></journal-title-group>
      <issn pub-type="epub">2978-4387</issn>
      <publisher><publisher-name>Caravel Press</publisher-name></publisher>
    </journal-meta>
    <article-meta>
      <article-id pub-id-type="doi">10.65582/set.2005.128</article-id>
      <article-id pub-id-type="publisher-id">2005.128</article-id>
      <title-group><article-title>Simulation and Analysis of the Heat Pump System with Flash-Tank Coupled with Scroll Compressor</article-title></title-group>
    <contrib-group>
      <contrib contrib-type="author">
        <name><surname>Yu</surname><given-names>Lihua</given-names></name>
        <xref ref-type="aff" rid="aff1"/>
      </contrib>
      <contrib contrib-type="author">
        <name><surname>Zhao</surname><given-names>Huixia</given-names></name>
        <xref ref-type="aff" rid="aff1"/>
      </contrib>
      <contrib contrib-type="author">
        <name><surname>Ma</surname><given-names>Guoyuan</given-names></name>
        <xref ref-type="aff" rid="aff1"/>
      </contrib>
      <aff id="aff1">College of Environmental and Energy Engineering, Beijing University of Technology, Beijing, China</aff>
    </contrib-group>
      <pub-date publication-format="electronic" date-type="pub"><day>23</day><month>09</month><year>2005</year></pub-date>
      <volume>4</volume>
      <issue>1</issue>
      <isbn publication-format="electronic">978-7-112-07718-2</isbn>
      <fpage>582</fpage>
      <lpage>585</lpage>
      <self-uri xlink:href="https://caravelpress.com/proceedings/set/papers/2005.128"/>
      <history>
        <date date-type="received"><string-date>23 September 2005</string-date></date>
      </history>
      <permissions>
        <copyright-statement>© 2005 Copyright WSSET</copyright-statement>
        <copyright-year>2005</copyright-year>
      </permissions>
      <abstract><p>The heat pump system with flash-tank coupled with scroll compressor has good performances, especially under the conditions of low ambient temperature, by improving its internal compression process. The correlation of electric efficiency is fitted by least square method based on the experimental data of the heat pump prototype in which R22 is used as refrigerant. According to the correlation, the performances of the heat pump system have been simulated and analyzed under the conditions of the condensation temperature from 30°C to 50°C and the evaporation temperature from -30°C to 0°C. The results demonstrate as follows: the heating coefficient of performance of the heat pump system is 1.87, the discharge temperature of the compressor is less than 130°C, the power input is 4.44kW, and the heating capacity is 8.28kW, when the system with a 5Hp scroll compressor worked in the condition of the condensation temperature of 45°C and the evaporation temperature of -25°C. So the heat pump system with high efficiency will be an ideal alternative method for building heating in cold regions such as north China and Yellow River basin.</p></abstract>
      <kwd-group kwd-group-type="author">
        <kwd>heat pump</kwd>
        <kwd>scroll compressor</kwd>
        <kwd>performance simulation</kwd>
      </kwd-group>
      <conference>
        <conf-date>23 to 25 September 2005</conf-date>
        <conf-name>4th International Conference on Sustainable Energy Technologies</conf-name>
        <conf-acronym>SET2005</conf-acronym>
        <conf-num>4</conf-num>
        <conf-loc>Jinan, China</conf-loc>
      </conference>
    </article-meta>
  </front>
  <body>
  </body>
  <back>
    <ref-list>
      <ref id="ref-r1">
        <mixed-citation publication-type="journal">Ma Guoyuan, Shao Shuang-quan. 2002.2. The study on heat pump for air conditioning in cold regions. Acta Energiae Solaris Sinica. pp17-21. China.</mixed-citation>
      </ref>
      <ref id="ref-r2">
        <mixed-citation publication-type="journal">Ma Guoyuan. 2001.The Study on adaptability of air-source heat pump of low ambient temperature. Postdoctor Research Report, Tsinghua University, China.</mixed-citation>
      </ref>
      <ref id="ref-r3">
        <mixed-citation publication-type="journal">Chai Qinhu. 2003. Theory analysis and experimental study on the quasi-two stage heat pump system. Master Degree Thesis. Tsinghua University, China.</mixed-citation>
      </ref>
      <ref id="ref-r4">
        <mixed-citation publication-type="journal">Zhao Huixia, Liu Si-guang, Ma Guoyuan. 2005. Experimental study on pump cycle of flash-tank economizer with scroll compressor. 8th International Energy Agency Heat Pump Conference. USA.</mixed-citation>
      </ref>
    </ref-list>
  </back>
</article>