<?xml version="1.0" encoding="UTF-8"?>
<!DOCTYPE article PUBLIC "-//NLM//DTD JATS (Z39.96) Journal Publishing DTD v1.3 20210610//EN" "JATS-journalpublishing1-3.dtd">
<article xmlns:xlink="http://www.w3.org/1999/xlink" xmlns:mml="http://www.w3.org/1998/Math/MathML" dtd-version="1.3" article-type="research-article" xml:lang="en">
  <front>
    <journal-meta>
      <journal-title-group><journal-title>SET Proceedings</journal-title></journal-title-group>
      <issn pub-type="epub">2978-4387</issn>
      <publisher><publisher-name>Caravel Press</publisher-name></publisher>
    </journal-meta>
    <article-meta>
      <article-id pub-id-type="doi">10.65582/set.2008.248</article-id>
      <article-id pub-id-type="publisher-id">2008.248</article-id>
      <title-group><article-title>A Study of the Cooling and Heating Performance of a Two-Stage Screw Heat Pump Using Treated sewage Water</article-title></title-group>
    <contrib-group>
      <contrib contrib-type="author">
        <name><surname>Kim</surname><given-names>Ji-Young</given-names></name>
        <xref ref-type="aff" rid="aff1"/>
        <email>bigkjy@kier.re.kr</email>
      </contrib>
      <contrib contrib-type="author">
        <name><surname>Baik</surname><given-names>Young-Jin</given-names></name>
        <xref ref-type="aff" rid="aff1"/>
        <email>twinjin@kier.re.kr</email>
      </contrib>
      <contrib contrib-type="author">
        <name><surname>Lee</surname><given-names>Young-Soo</given-names></name>
        <xref ref-type="aff" rid="aff1"/>
        <email>yslee@kier.re.kr</email>
      </contrib>
      <contrib contrib-type="author">
        <name><surname>Chang</surname><given-names>Ki-Chang</given-names></name>
        <xref ref-type="aff" rid="aff1"/>
        <email>kcchang@kier.re.kr</email>
      </contrib>
      <contrib contrib-type="author">
        <name><surname>Ra</surname><given-names>Ho-Sang</given-names></name>
        <xref ref-type="aff" rid="aff1"/>
        <email>hsra@kier.re.kr</email>
      </contrib>
      <aff id="aff1">Korea Institute of Energy Research, Daejeon, Korea</aff>
    </contrib-group>
      <pub-date publication-format="electronic" date-type="pub"><day>24</day><month>08</month><year>2008</year></pub-date>
      <volume>7</volume>
      <issue>1</issue>
      <isbn publication-format="electronic">978-1-995850-08-5</isbn>
      <fpage>1789</fpage>
      <lpage>1794</lpage>
      <self-uri xlink:href="https://caravelpress.com/proceedings/set/papers/2008.248"/>
      <history>
        <date date-type="received"><string-date>24 August 2008</string-date></date>
      </history>
      <permissions>
        <copyright-statement>© 2008 Copyright WSSET</copyright-statement>
        <copyright-year>2008</copyright-year>
      </permissions>
      <abstract><p>The treated sewage water temperature is about 5℃ lower in summer and 5~10℃ higher in winter than ambient air. It can be used as a high-performance heat pump heat source. In this study, a 100RT two-stage compression heat pump was developed using a treated sewage water heat source and system applicable to sewage disposal plants. Although a heat pump performs better than general heat pump, the large temperature difference between its load and source degrades its performance. To solve this problem, two-stage screw compression is considered. The experiment focused on the system’s operating performance variations over the water supply and the temperature of the treated sewage water in the field. The results showed that the system’s cooling and heating performance is higher than that of general heat pumps and is enough to supply 70℃ water.</p></abstract>
      <kwd-group kwd-group-type="author">
        <kwd>Treated sewage water</kwd>
        <kwd>2-stage compression</kwd>
        <kwd>Heat pump</kwd>
        <kwd>COP</kwd>
      </kwd-group>
      <conference>
        <conf-date>24 to 27 August 2008</conf-date>
        <conf-name>7th International Conference on Sustainable Energy Technologies</conf-name>
        <conf-acronym>SET2008</conf-acronym>
        <conf-num>7</conf-num>
        <conf-loc>Seoul, Korea</conf-loc>
      </conference>
    </article-meta>
  </front>
  <body>
  </body>
  <back>
    <ref-list>
      <ref id="ref-r1">
        <mixed-citation publication-type="journal">Y.S. Lee, J,R Kim, K.C. Chang, W.H. Lee, H.S. RA, Y.J. Baik, 2004, Performance Test of 2-Stage Heat Pump System using River Water as a Heat Source, Society of Air-Conditioning and Refrigerating Engineers of Korea, 2004 Summer Conference, pp. 1288～1293. Korea.</mixed-citation>
      </ref>
      <ref id="ref-r2">
        <mixed-citation publication-type="journal">J.R. Kim, Y.S. Lee, H.s. Ra, Y.J. Baik, 2005, Research on Performance Test of 2-Stage Heat Pump System using River Water as a Heat Source, Journal of The Society of Air-Conditioning and Refrigerating Engineers of Korea, Vol 35, pp. 214～219. Korea.</mixed-citation>
      </ref>
      <ref id="ref-r3">
        <mixed-citation publication-type="journal">Y.S. Chang, Y.C. Lee, Y.G. Kim, 2003, Part-Load Performance Test of a Screw Chiller with Economizer using R22 and R407C, Journal of The Society of Air-Conditioning and Refrigerating Engineers of Korea, Vol 15, No. 15, pp. 902-909. Korea.</mixed-citation>
      </ref>
      <ref id="ref-r4">
        <mixed-citation publication-type="journal">J.H. Ha, Y.C. Kim, J.M. Choi, 1999, Experimental study on the superheat control of the vairable speed heat pump, Proceedings of the SAREK winter annual conference pp. 527-533. Korea.</mixed-citation>
      </ref>
      <ref id="ref-r5">
        <mixed-citation publication-type="journal">D. S. Young, G. B. Lee, M. S. Kim, Y. M. Cho, W. H. Lee, Y. J. Hwang, B. Y. Chung, 2004, A Study on the Capacity of Variable. Speed Vapor Compressor System using superheat at the Compressor Discharge Proceedings of the SAREK winter annual conference pp. 552-547. Korea.</mixed-citation>
      </ref>
      <ref id="ref-r6">
        <mixed-citation publication-type="journal">Park, C. S., 2007, Performance Characteristics of 2 Two-Stage Compression Heat Pump System Using River Water, Ph.D thesis, Korea University, Korea.</mixed-citation>
      </ref>