<?xml version="1.0" encoding="UTF-8"?>
<!DOCTYPE article PUBLIC "-//NLM//DTD JATS (Z39.96) Journal Publishing DTD v1.3 20210610//EN" "JATS-journalpublishing1-3.dtd">
<article xmlns:xlink="http://www.w3.org/1999/xlink" xmlns:mml="http://www.w3.org/1998/Math/MathML" dtd-version="1.3" article-type="research-article" xml:lang="en">
  <front>
    <journal-meta>
      <journal-title-group><journal-title>SET Proceedings</journal-title></journal-title-group>
      <issn pub-type="epub">2978-4387</issn>
      <publisher><publisher-name>Caravel Press</publisher-name></publisher>
    </journal-meta>
    <article-meta>
      <article-id pub-id-type="doi">10.65582/set.2009.013</article-id>
      <article-id pub-id-type="publisher-id">2009.013</article-id>
      <title-group><article-title>Performance characteristics of carbon dioxide transcritical heat pump cycle with an expander</article-title></title-group>
    <contrib-group>
      <contrib contrib-type="author">
        <name><surname>Huan</surname><given-names>Z</given-names></name>
        <xref ref-type="aff" rid="aff1"/>
      </contrib>
      <aff id="aff1">Department of Mechanical Engineering, Vaal University of Technology, Private Bag X021, Vanderbijlpark 1900, South Africa</aff>
    </contrib-group>
      <pub-date publication-format="electronic" date-type="pub"><day>31</day><month>08</month><year>2009</year></pub-date>
      <volume>8</volume>
      <isbn publication-format="electronic">978-3-9813246-1-7</isbn>
      <fpage>1</fpage>
      <lpage>6</lpage>
      <self-uri xlink:href="https://caravelpress.com/proceedings/set/papers/2009.013"/>
      <history>
        <date date-type="received"><string-date>31 August 2009</string-date></date>
      </history>
      <permissions>
        <copyright-statement>© 2009 Copyright WSSET</copyright-statement>
        <copyright-year>2009</copyright-year>
      </permissions>
      <abstract><p>Due to the low coefficient of the performance compared with conventional refrigerant systems, new technology, such as the thermal expander, was suggested to be employed to improve the performance of CO2 system, which has been one of the most promising technologies in replace of the working fluids. Experiments were carried out on the CO2 transcritical cycle with a designed novel expander at the condition of water source heat pump in order to study the performance characteristics of CO2 expander, its influences on the entire system, and the performance characteristics of the system at the variable environmental conditions. The results show that the suggested CO2 expander has the attractive potential to improve the performance of the CO2 transcritical cycle, the efficiency of expander is mainly dependant on the rotational speed, and the maximum efficiency of the expander can be reached by the optimization of the operational condition. Furthermore the expander has an important impact on the implementation of the entire system. Based on the obtained results, it was implied that the performance of the system is the total integrated effect of all factors, and the optimization of operational parameters is in further investigation.</p></abstract>
      <kwd-group kwd-group-type="author">
        <kwd>CO2 transcritical cycle</kwd>
        <kwd>heat pump</kwd>
        <kwd>expander</kwd>
      </kwd-group>
      <conference>
        <conf-date>31 August to 3 September 2009</conf-date>