      <title-group><article-title>Energy Analysis of Two-Stage Cascade Refrigeration System Using R-1234yf and R-404a Refrigerant Couple</article-title></title-group>
    <contrib-group>
      <contrib contrib-type="author" corresp="yes">
        <contrib-id contrib-id-type="orcid">https://orcid.org/0000-0003-1340-1893</contrib-id>
        <name><surname>Kilicarslan</surname><given-names>Ali</given-names></name>
        <xref ref-type="aff" rid="aff1"/>
        <role vocab="credit" vocab-identifier="https://credit.niso.org/">Conceptualization</role>
        <role vocab="credit" vocab-identifier="https://credit.niso.org/">Methodology</role>
        <role vocab="credit" vocab-identifier="https://credit.niso.org/">Investigation</role>
        <role vocab="credit" vocab-identifier="https://credit.niso.org/">Formal analysis</role>
        <role vocab="credit" vocab-identifier="https://credit.niso.org/">Writing (original draft)</role>
        <role vocab="credit" vocab-identifier="https://credit.niso.org/">Writing (review and editing)</role>
        <role vocab="credit" vocab-identifier="https://credit.niso.org/">Supervision</role>
        <email>alikilicarslan@hitit.edu.tr</email>
      </contrib>
      <contrib contrib-type="author">
        <name><surname>Kaplan</surname><given-names>Tahir</given-names></name>
        <xref ref-type="aff" rid="aff1"/>
        <role vocab="credit" vocab-identifier="https://credit.niso.org/">Writing (original draft)</role>
        <role vocab="credit" vocab-identifier="https://credit.niso.org/">Investigation</role>
        <email>tkaplan529@gmail.com</email>
      </contrib>
      <aff id="aff1"><institution-wrap><institution>Hitit University, Faculty of Engineering and Natural Sciences, Department of Mechanical Engineering, 19030 Çevre Yolu, Çorum, Türkiye</institution><institution-id institution-id-type="ror">https://ror.org/01x8m3269</institution-id></institution-wrap></aff>
    </contrib-group>
      <pub-date publication-format="electronic" date-type="pub"><day>23</day><month>11</month><year>2026</year></pub-date>
      <volume>22</volume>
      <isbn publication-format="electronic">978-1-995850-00-9</isbn>
      <fpage>27</fpage>
      <lpage>37</lpage>
      <self-uri xlink:href="https://caravelpress.com/proceedings/set/papers/2026.003"/>
      <history>
        <date date-type="received"><day>10</day><month>2</month><year>2026</year></date>
        <date date-type="rev-recd"><day>17</day><month>3</month><year>2026</year></date>
        <date date-type="accepted"><day>29</day><month>3</month><year>2026</year></date>
      </history>
      <permissions>
        <copyright-statement>© 2026 The Author(s). Published by Caravel Press.</copyright-statement>
        <copyright-year>2026</copyright-year>
        <license license-type="open-access" xlink:href="https://creativecommons.org/licenses/by/4.0/">
          <license-p>This is an open access article under the CC BY 4.0 licence.</license-p>
        </license>
      </permissions>
      <abstract><p>Vapor compression cascade refrigeration systems consist of a low-temperature refrigeration cycle (LTC) and a high-temperature refrigeration cycle (HTC). Two-stage vapor-compression cascade refrigeration cycles (CRCs) are commonly used in low-temperature applications. In this study, R-404a is used in the LTC, and R-1234yf is used in the HTC. The effects of the outdoor air temperature on the suction and discharge pressures of HTC and LTC, powers drawn by the compressors of HTC and LTC, heat rejection capacity of the condenser of CRC, heat absorption capacity of the evaporator of CRC, coefficient of performance (COP) of CRC, the mass flow rates of refrigerants circulating through HTC and LTC were experimentally investigated in terms of the 1st Law of thermodynamics. The results show that increasing the outlet air temperature from 28 °C to 43.5 °C results in significant changes in system parameters. As the outdoor air temperature increased, the suction and discharge pressures of HTC and LTC, the powers drawn by the compressors of HTC and LTC, the heat rejection capacity of the condenser of CRC, the mass flow rates of refrigerants circulating through HTC and LTC increased. In contrast, the heat absorption capacity of the evaporator of CRC and the COP of CRC decreased. The largest increase was observed in the investigated parameters, with HTC discharge and suction pressures increasing by 41.94% and 31.11%, respectively.</p></abstract>
      <kwd-group kwd-group-type="author">
        <kwd>Cascade refrigeration</kwd>
        <kwd>Two-stage</kwd>
        <kwd>Energy analysis</kwd>
        <kwd>Outdoor air temperature</kwd>
        <kwd>R1234yf</kwd>
        <kwd>R404a</kwd>
      </kwd-group>
      <funding-group>
        <funding-statement>This research received no specific funding.</funding-statement>
      </funding-group>
      <conference>
        <conf-date>13 to 15 August 2026</conf-date>
        <conf-name>22nd International Conference on Sustainable Energy Technologies</conf-name>
        <conf-acronym>SET2026</conf-acronym>
        <conf-num>22</conf-num>
        <conf-loc>Kuala Lumpur, Malaysia</conf-loc>
      </conference>
    </article-meta>
  </front>
  <body>
    <sec id="sec1">
      <title>Introduction</title>
      <p>The inability of single-stage vapor-compression refrigeration systems to meet low-temperature requirements economically and efficiently has accelerated the development of two-stage vapor-compression cascade refrigeration systems as an alternative. Cascade refrigeration systems are widely preferred, especially for low-temperature applications (−50 °C to −100 °C) (<xref ref-type="bibr" rid="ref-5807403a-6aa1-46a2-8733-dcf30d2d59fe">Yılmaz <italic>et al.</italic> 2020</xref>). The main application areas of these systems include blood and medical product storage, gas liquefaction, and heat treatment (hardening) of special alloy steels (<xref ref-type="bibr" rid="ref-dbed100e-6e42-4346-ae88-2665966d1c32">Gupta 1985</xref>). A two-stage cascade refrigeration system consists of two compressors, a condenser, an evaporator, two expansion valves, and a cascade heat exchanger connecting the cycles. This heat exchanger serves as the condenser for the low-temperature circuit (LTC) and simultaneously functions as the evaporator for the high-temperature circuit (HTC), facilitating heat transfer between the two cycles. There are studies related to the vapor compression cascade refrigeration cycles in the literature. The most relevant ones are summarized below.</p>
      <p>In a theoretical study, a two-stage cascade system using the R1150/R717 refrigerant pair was investigated as an alternative to a three-stage system with the R1150/R41/R717 refrigerant group, and it was determined that the total compressor power of the two-stage system was 1.45–1.61 kW lower. The coefficient of performance (COP) was 7.0% to 11.7% higher (<xref ref-type="bibr" rid="ref-e199f79b-928d-4ed7-a433-bd805eb54bf8">Sun and Wang 2022a</xref>). In a study where thermodynamic simulations of six different cycle architectures (single-stage with/without heat exchanger, two-stage cascade with vapor and liquid injection, parallel compression cascade with/without economizer) were performed at very low temperatures, R290 was used in the upper cycle and R170 in the lower cycle. In the study, it was observed that the optimum intermediate-stage cascade temperature ranged from 20 °C to 37 °C, depending on the cycle type, and that this directly affected energy performance. In addition, it has been determined that the energy performance of parallel compression cascade cycles is higher than that of single-stage cycles but 20% to 30% lower than that of stage compression cascade cycles (<xref ref-type="bibr" rid="ref-3daee716-069b-475b-9502-2e1625a1319b">Udroiu <italic>et al.</italic> 2022</xref>).</p>
      <p>In an experimental study in which R452a was used in the upper circuit and a conventional R23 or CO2 sublimation cycle in the lower-temperature cycle, it was reported that the preference for CO2 sublimation in the lower-temperature cycle positively affected system performance (<xref ref-type="bibr" rid="ref-08d80516-2205-44b5-ac4a-058232cab77b">Xu <italic>et al.</italic> 2021</xref>). In a study comparing the energy and exergy parameters of different refrigerant pairs (R152a–R23, R290–R23, R507–R23, R234a–R23, R717–R23, and R404a–R23); it was observed that the COP value increased in all refrigerant pairs depending on the increasing polytropic efficiency and evaporator temperature, while the exergy destruction due to irreversibilities decreased. Among the alternatives examined, the R717–R23 pair yielded the best results, with the maximum COP and minimum exergy destruction rate (<xref ref-type="bibr" rid="ref-5eca1b1b-d9a4-4e27-9c14-457b50ff952b">Kilicarslan and Hosoz 2010</xref>).</p>
      <p>Symmetric cascade systems (R125/R125, R1270/R1270, R143a/R143a, R404a/R404a, R407a/R407a, R410a/R410a, and R507a/R507a) using the same fluid in the upper and lower circuits were compared with the conventional R23/R404a cascade system. Performance improvement rates were calculated as 19.48%, 8.08%, 21.54%, 14.33%, 11.00%, 15.64%, and 12.11%, respectively (<xref ref-type="bibr" rid="ref-51d7d9c1-3ab6-4345-b8ad-f5a359ee87ea">Sun <italic>et al.</italic> 2022b</xref>). In an experimental study, low-GWP R513a, R1234yf, and R436a were used as alternatives to R134a in the upper circuit, and R744 (CO2) was used in the lower circuit. In contrast, the use of R436a resulted in a 3.1% increase in system performance; the use of R1234yf and R513a decreased performance by 3.7% and 4.4%, respectively (<xref ref-type="bibr" rid="ref-7cad5ad0-bd41-4434-b478-34ff503016d6">Blanco Ojeda <italic>et al.</italic> 2022</xref>).</p>
      <p>In another theoretical study conducted at different evaporation and condensation temperatures, the fluids R32, R1234yf, R1234ze, R161, R1270, R290, and R717 in the temperature cycle and R23, R41, and R170 in the low-temperature cycle were examined in terms of energy and exergy. The analysis results showed that the combination of R161 in the upper cycle and R41 and R170 in the lower cycle was the most suitable option (<xref ref-type="bibr" rid="ref-d20687bd-b683-481e-9cc0-bd8c661ec86a">Sun <italic>et al.</italic> 2019</xref>).</p>
      <p>In a modeling study comparing traditional R404a and R134a refrigerants with low GWP natural alternatives (R717, R744, R290) and synthetic refrigerants (R1234ze and R152a) in terms of energy and TEWI (Total Equivalent Environmental Impact) parameters, it was predicted that future cooling solutions will rely on low GWP refrigerants. However, it was emphasized that these refrigerants pose risks, including toxicity and flammability, and that the most stable and promising refrigerant for the subcycle of central cascade systems is CO2 (R744) (<xref ref-type="bibr" rid="ref-8da7c994-5797-42b5-868c-e1f67cff30d3">Llopis <italic>et al.</italic> 2015</xref>). The refrigerant pairs R41-R161, R41-R1234yf, R41-R1234ze, R744-R161, R744-R1234yf, and R744-R1234ze. In a study in which energy, exergy, economy, and environment (4E) analyses were performed, the maximum COP (2.09) and the highest exergy efficiency (35.32%) were obtained at condensation temperatures of 40 °C and evaporation temperatures of −30 °C. In the study, R41-R161 and R41-R1234ze stood out as optimum fluid pairs (<xref ref-type="bibr" rid="ref-7c09abd6-5a84-420e-9928-97d8673a1f51">Deymi-Dashtebayaz <italic>et al.</italic> 2021</xref>).</p>
      <p>When the literature summarized above is examined, it is evident that most studies on two-stage vapor-compression cascade refrigeration systems are theoretical and simulation-based. The limited number of experimental studies stems from the difficulties in setting up test setups, high costs, and operational risks. In particular, when research on the use of R-1234yf refrigerant, a current and environmentally friendly alternative with low global warming potential (GWP), in cascade systems is reviewed, it is observed that existing studies remain almost entirely at the theoretical level, and parametric evaluations are generally limited only to evaporator and condenser temperatures. This situation indicates a significant gap in the literature regarding the experimental validation of the performance of new-generation refrigerants under real operating conditions.</p>
      <p>This experimental study differs from studies in the literature: the environmentally friendly refrigerant R-1234yf will be used in the upper circuit of a two-stage vapor-compression cascade refrigeration system, and the refrigerant R-404a, which performs well at low temperatures, will be used in the lower circuit. Another novelty of this study is that the effect of outside air temperature up to 45 °C is investigated in a two-stage vapor-compression cascade refrigeration system. The effect of outside air temperature on the inlet and outlet pressures of the compressors, the power consumed by the compressors, the flow rates of the refrigerant filling the system, the evaporator and condenser capacity, and the cooling efficiency will be investigated experimentally. The results will be obtained by developing a computer code using Engineering Equation Solver, EES (<xref ref-type="bibr" rid="ref-6ae5a864-4fe8-41c7-bdad-7a42f4e680f4">Klein 2020</xref>).</p>
    </sec>
    <sec id="sec2">
      <title>Materials and Method</title>
      <p>Vapor compression cascade refrigeration systems are used to maintain media, materials, or fluids at very low temperatures. Depending on the desired low temperature, vapor-compression cascade refrigeration systems can have 2, 3, or more cascade stages. The method used in this study will be based on the two-stage vapor compression cascade refrigeration system shown in Figure 1 below. The method consists of three stages. In the first stage, a thermodynamic model incorporating energy analysis will be developed. In the second stage, a computer program based on the thermodynamic model and accounting for the system's operating points will be developed using the Engineering Equation Solver (EES). In the third stage, experimental studies will be conducted.</p>
      <fig id="fig1">
        <label>Figure 1</label>
        <caption><p>Experimental setup of a two-stage vapor compression cascade refrigeration system.</p></caption>
        <graphic xlink:href="obj/4e/7c/4e7cbcfb0b1d75a01cf3bd05c1525ed1715c685cb0d2ba2f8ab4aedd8104be4b"/>
      </fig>
      <p>The condenser of the cascade refrigeration system will be placed inside a duct through which air is passed, with electric heaters located there. After the high-temperature cycle (HTC) of the cascade system is vacuumed, R1234yf refrigerant will be charged, and after the low-temperature cycle (LTC) is vacuumed, R-404a refrigerant will be charged. The cascade refrigeration system will be started and allowed to reach steady-state conditions. The heaters installed in the condenser will be activated to maintain air temperatures between 25 °C and 35 °C. Temperature and pressure measurements will be taken at the operating points of the cascade refrigeration system under varying air temperatures, and mass flow rate measurements will be taken in the liquid line. These measurements will be repeated at least three times under the same conditions. Thermophysical properties of the selected refrigerants for HTC and LTC are given in Table 1.</p>
      <table-wrap id="tbl1">
        <label>Table 1</label>
        <caption><p>Thermo-physical properties of the selected refrigerants adapted from (<xref ref-type="bibr" rid="ref-6ae5a864-4fe8-41c7-bdad-7a42f4e680f4">Klein 2020</xref>; <xref ref-type="bibr" rid="ref-76137130-7020-4875-bff6-1d8b6ab30c92">Wikipedia no date</xref>).</p></caption>
        <table>
          <thead>
            <tr>
              <th>Refrigerant</th>
              <th>ODP</th>
              <th>GWP</th>
              <th>Safety group</th>
              <th>Boiling point (°C)</th>
              <th>Critical Temperature (°C)</th>
              <th>Critical Pressure (kPa)</th>
            </tr>
          </thead>
          <tbody>
            <tr>
              <td>R-1234yf</td>
              <td>0</td>
              <td>&lt;1</td>
              <td>A2L</td>
              <td>−29.48</td>
              <td>94.7</td>
              <td>3382</td>
            </tr>
            <tr>
              <td>R-404a</td>
              <td>0</td>
              <td>3922</td>
              <td>A1</td>
              <td>−46.22</td>
              <td>72.12</td>
              <td>3735</td>
            </tr>
          </tbody>
        </table>
      </table-wrap>
      <p>In this study, a two-stage vapor compression cascade refrigeration system will be experimentally investigated. Figure 2 schematically shows the experimental setup of the two-stage vapor compression cascade refrigeration system. This refrigeration system consists of two compressors, two expansion valves, a condenser, an evaporator, and a heat exchanger. As seen in Figure 1, the cascade refrigeration system consists of a low-temperature cycle and a high-temperature cycle.</p>
      <fig id="fig2">
        <label>Figure 2</label>
        <caption><p>Schematic representation of the experimental setup of a two-stage vapor compression cascade refrigeration cycle.</p></caption>
        <graphic xlink:href="obj/9f/1c/9f1c863f0d52b94fdb2652363979c7c66a4f5b3d0846945c420c65afa5efb5a4"/>
      </fig>
    </sec>
    <sec id="sec3">
      <title>Thermodynamic Analysis</title>
      <p>In a two-stage vapor compression cascade refrigeration system, it is assumed that the thermodynamic properties of the fluid do not change with time at any point in the system (steady regime), that changes in kinetic and potential energies between the inlet and outlet of the elements forming the cascade system are neglected, that pressure losses are neglected, and that the compressors are adiabatic. Applying the assumptions stated in the paragraph above, the energy, entropy, and second law equations for the elements forming the cascade refrigeration system are written as follows,</p>
      <disp-formula id="eq1">
        <label>(1)</label>
        <math display="block" class="tml-display" style="display:block math"><mrow><mtext>Compressor (LTC):</mtext><mspace width="1em"></mspace><msub><mover><mi>W</mi><mo stretchy="false" class="wbk-acc" style="math-depth:0">˙</mo></mover><mrow><mi>L</mi><mi>T</mi><mi>C</mi></mrow></msub><mo>=</mo><msub><mover><mi>m</mi><mo stretchy="false" class="wbk-acc" style="math-depth:0">˙</mo></mover><mrow><mi>L</mi><mi>T</mi><mi>C</mi></mrow></msub><mrow><mo fence="true" form="prefix" stretchy="true">(</mo><msub><mi>h</mi><mn>1</mn></msub><mo>−</mo><msub><mi>h</mi><mn>2</mn></msub><mo fence="true" form="postfix" stretchy="true">)</mo></mrow></mrow></math>
      </disp-formula>
      <disp-formula id="eq2">
        <label>(2)</label>
        <math display="block" class="tml-display" style="display:block math"><mrow><mtext>Compressor (HTC):</mtext><mspace width="1em"></mspace><msub><mover><mi>W</mi><mo stretchy="false" class="wbk-acc" style="math-depth:0">˙</mo></mover><mrow><mi>H</mi><mi>T</mi><mi>C</mi></mrow></msub><mo>=</mo><msub><mover><mi>m</mi><mo stretchy="false" class="wbk-acc" style="math-depth:0">˙</mo></mover><mrow><mi>H</mi><mi>T</mi><mi>C</mi></mrow></msub><mrow><mo fence="true" form="prefix" stretchy="true">(</mo><msub><mi>h</mi><mn>6</mn></msub><mo>−</mo><msub><mi>h</mi><mn>5</mn></msub><mo fence="true" form="postfix" stretchy="true">)</mo></mrow></mrow></math>
      </disp-formula>
      <disp-formula id="eq3">
        <label>(3)</label>
        <math display="block" class="tml-display" style="display:block math"><mrow><mtext>Condenser (CRC):</mtext><mspace width="1em"></mspace><msub><mover><mi>Q</mi><mo stretchy="false" style="math-depth:0">˙</mo></mover><mi>c</mi></msub><mo>=</mo><msub><mover><mi>m</mi><mo stretchy="false" class="wbk-acc" style="math-depth:0">˙</mo></mover><mrow><mi>H</mi><mi>T</mi><mi>C</mi></mrow></msub><mrow><mo fence="true" form="prefix" stretchy="true">(</mo><msub><mi>h</mi><mn>7</mn></msub><mo>−</mo><msub><mi>h</mi><mn>6</mn></msub><mo fence="true" form="postfix" stretchy="true">)</mo></mrow></mrow></math>
      </disp-formula>
      <disp-formula id="eq4">
        <label>(4)</label>
        <math display="block" class="tml-display" style="display:block math"><mrow><mtext>Evaporator (CRC):</mtext><mspace width="1em"></mspace><msub><mover><mi>Q</mi><mo stretchy="false" style="math-depth:0">˙</mo></mover><mi>e</mi></msub><mo>=</mo><msub><mover><mi>m</mi><mo stretchy="false" class="wbk-acc" style="math-depth:0">˙</mo></mover><mrow><mi>L</mi><mi>T</mi><mi>C</mi></mrow></msub><mrow><mo fence="true" form="prefix" stretchy="true">(</mo><msub><mi>h</mi><mn>1</mn></msub><mo>−</mo><msub><mi>h</mi><mn>4</mn></msub><mo fence="true" form="postfix" stretchy="true">)</mo></mrow></mrow></math>
      </disp-formula>
      <disp-formula id="eq5">
        <label>(5)</label>
        <math display="block" class="tml-display" style="display:block math"><mrow><mtext>Heat exchanger (CRC):</mtext><mspace width="1em"></mspace><msub><mover><mi>m</mi><mo stretchy="false" class="wbk-acc" style="math-depth:0">˙</mo></mover><mn>1</mn></msub><mrow><mo fence="true" form="prefix" stretchy="true">(</mo><msub><mi>h</mi><mn>2</mn></msub><mo>−</mo><msub><mi>h</mi><mn>3</mn></msub><mo fence="true" form="postfix" stretchy="true">)</mo></mrow><mo>=</mo><msub><mover><mi>m</mi><mo stretchy="false" class="wbk-acc" style="math-depth:0">˙</mo></mover><mn>2</mn></msub><mrow><mo fence="true" form="prefix" stretchy="true">(</mo><msub><mi>h</mi><mn>5</mn></msub><mo>−</mo><msub><mi>h</mi><mn>8</mn></msub><mo fence="true" form="postfix" stretchy="true">)</mo></mrow></mrow></math>
      </disp-formula>
      <disp-formula id="eq6">
        <label>(6)</label>
        <math display="block" class="tml-display" style="display:block math"><mrow><mtext>Expansion valve (LTC):</mtext><mspace width="1em"></mspace><msub><mi>h</mi><mn>3</mn></msub><mo>=</mo><msub><mi>h</mi><mn>4</mn></msub></mrow></math>
      </disp-formula>
      <disp-formula id="eq7">
        <label>(7)</label>
        <math display="block" class="tml-display" style="display:block math"><mrow><mtext>Expansion valve (HTC):</mtext><mspace width="1em"></mspace><msub><mi>h</mi><mn>7</mn></msub><mo>=</mo><msub><mi>h</mi><mn>8</mn></msub></mrow></math>
      </disp-formula>
      <disp-formula id="eq8">
        <label>(8)</label>
        <math display="block" class="tml-display" style="display:block math"><mrow><mpadded lspace="0"><mi>COP</mi></mpadded><mo>=</mo><mfrac><msub><mover><mi>Q</mi><mo stretchy="false" style="math-depth:0">˙</mo></mover><mi>e</mi></msub><mrow><msub><mover><mi>W</mi><mo stretchy="false" class="wbk-acc" style="math-depth:0">˙</mo></mover><mrow><mi>L</mi><mi>T</mi><mi>C</mi></mrow></msub><mo>+</mo><msub><mover><mi>W</mi><mo stretchy="false" class="wbk-acc" style="math-depth:0">˙</mo></mover><mrow><mi>H</mi><mi>T</mi><mi>C</mi></mrow></msub></mrow></mfrac></mrow></math>
      </disp-formula>
      <p>Where:</p>
      <list list-type="bullet">
        <list-item><p>h = the specific enthalpy at the operating points (1, 2, …, 8) (kJ/kg)</p></list-item>
        <list-item><p>ṁ<sub>LTC</sub> = the mass flow rates in the low-temperature in LTC (kg/s)</p></list-item>
        <list-item><p>ṁ<sub>HTC</sub> = the mass flow rates in the high-temperature in HTC (kg/s)</p></list-item>
        <list-item><p>Ẇ<sub>LTC</sub> = the power consumed by the compressor in the low-temperature (kW)</p></list-item>
        <list-item><p>Ẇ<sub>HTC</sub> = the power consumed by the compressor in the high-temperature (kW)</p></list-item>
        <list-item><p>Q̇e = the refrigeration capacity of the two-stage vapor compression cascade refrigeration (CRC) (kW)</p></list-item>
        <list-item><p>Q̇c = the amount of heat released to the environment by the CRC condenser (kW)</p></list-item>
        <list-item><p>COP = the coefficient of performance of the CRC.</p></list-item>
      </list>
    </sec>
    <sec id="sec4">
      <title>Uncertainty Analysis</title>
      <p>Holman (<xref ref-type="bibr" rid="ref-0246feb1-908a-4176-9a3f-9a8e562b9ed6">1984</xref>) presents uncertainty analysis in detail. Assume that the experimental result <italic>G</italic> is a function of n measured variables <inline-formula><tex-math><![CDATA[x_{1}, x_{2}, x_{3}, \ldots, x_{n}]]></tex-math></inline-formula>. Therefore,</p>
      <disp-formula id="eq9">
        <label>(9)</label>
        <tex-math><![CDATA[G = G\left(x_{1}, x_{2}, x_{3}, \ldots, x_{n}\right)]]></tex-math>
      </disp-formula>
      <p>Suppose that Y<sub>R</sub> is the uncertainty in the experimental result and Y<sub>1</sub>, Y<sub>2</sub>, Y<sub>3</sub>,…, Y<sub>n</sub> are the uncertainties in the measured variables. If the uncertainties in the measured variables are all specified with the same probability, the uncertainty in the experimental result with these probabilities can be expressed by (<xref ref-type="bibr" rid="ref-0246feb1-908a-4176-9a3f-9a8e562b9ed6">Holman 1984</xref>) as</p>
      <disp-formula id="eq10">
        <label>(10)</label>
        <tex-math><![CDATA[Y_{R} = \left[ \left( \frac{\partial G}{\partial x_{1}} Y_{1} \right)^{2} + \left( \frac{\partial G}{\partial x_{2}} Y_{2} \right)^{2} + \left( \frac{\partial G}{\partial x_{3}} Y_{3} \right)^{2} + \cdots + \left( \frac{\partial G}{\partial x_{n}} Y_{n} \right)^{2} \right]^{1/2}]]></tex-math>
      </disp-formula>
      <p>The uncertainties of the measuring devices that are used to calculate the uncertainties associated with <inline-formula><tex-math><![CDATA[{\dot{W}}_{LTC}]]></tex-math></inline-formula> , <inline-formula><tex-math><![CDATA[{\dot{W}}_{HTC}]]></tex-math></inline-formula> , <inline-formula><tex-math><![CDATA[{\dot{Q}}_{c}]]></tex-math></inline-formula> , <inline-formula><tex-math><![CDATA[{\dot{Q}}_{e}]]></tex-math></inline-formula> and COP are <imgi>obj/54/05/54059ea770ea668a9a200d07e5f44bfdeffe113ec9880408cb13013771dbcde7@6.9x7.1pt</imgi>1 % for turbine-type mass flow meter, <imgi>obj/54/05/54059ea770ea668a9a200d07e5f44bfdeffe113ec9880408cb13013771dbcde7@6.9x7.1pt</imgi>1 % for bourdon-type pressure gauge, and <imgi>obj/54/05/54059ea770ea668a9a200d07e5f44bfdeffe113ec9880408cb13013771dbcde7@6.9x7.1pt</imgi>1.5 % for K-type thermocouple. Maximum and minimum uncertainties of the parameters are determined by EES (<xref ref-type="bibr" rid="ref-6ae5a864-4fe8-41c7-bdad-7a42f4e680f4">Klein 2020</xref>). Minimum and maximum uncertainties of the parameters are given in Table 2.</p>
      <table-wrap id="tbl2">
        <label>Table 2</label>
        <caption><p>Minimum, maximum, and uncertainties in this experimental study.</p></caption>
        <table>
          <thead>
            <tr>
              <th>Parameters</th>
              <th>Minimum uncertainties</th>
              <th>Maximum uncertainties</th>
            </tr>
          </thead>
          <tbody>
            <tr>
              <td><inline-formula><tex-math><![CDATA[{\dot{W}}_{LTC}]]></tex-math></inline-formula></td>
              <td>1.589</td>
              <td>2.039</td>
            </tr>
            <tr>
              <td><inline-formula><tex-math><![CDATA[{\dot{W}}_{HTC}]]></tex-math></inline-formula></td>
              <td>5.058</td>
              <td>7.133</td>
            </tr>
            <tr>
              <td><inline-formula><tex-math><![CDATA[{\dot{Q}}_{c}]]></tex-math></inline-formula></td>
              <td>8.375</td>
              <td>10.79</td>
            </tr>
            <tr>
              <td><inline-formula><tex-math><![CDATA[{\dot{Q}}_{e}]]></tex-math></inline-formula></td>
              <td>4.337</td>
              <td>5.593</td>
            </tr>
            <tr>
              <td>COP</td>
              <td>0.02199</td>
              <td>0.02905</td>
            </tr>
          </tbody>
        </table>
      </table-wrap>
    </sec>
    <sec id="sec5">
      <title>Results and Discussion</title>
      <p>Experimentally measured average values were entered into a computer program developed with Engineering Equation Solver (EES) software, and parameters related to the First Law of Thermodynamics were obtained as a function of the outside air temperature passing through the condenser. R404a is used as the refrigerant in LTC, while R1234yf is used in HTC.</p>
      <p>In the following section, the results depicting the effects of the outdoor air temperatures ranging from 28 °C to 43.5 °C, on the suction and discharge pressures of HTC and LTC, powers drawn by the compressors of HTC and LTC, heat rejection capacity of the condenser of CRC, heat absorption capacity of the evaporator of CRC, coefficient of performance (COP) of CRC, the mass flow rates of refrigerants circulating through HTC and LTC are presented and discussed in detail.</p>
      <fig id="fig3">
        <label>Figure 3</label>
        <caption><p>Changes of compressor suction and discharge pressures as a function of outlet air temperature: (a) high temperature cycle (HTC); (b) low temperature cycle (LTC).</p></caption>
        <graphic xlink:href="obj/3b/af/3baf9a0a73d4e839f4be788edb1952ed86d94e9043a3b9693c7c07fbd3201093"/>
      </fig>
      <p>Figure 3 depicts the variation of the suction and discharge pressures of the high- and low-temperature cycles of a two-stage vapor compression cascade refrigeration cycle (CRC) with respect to the outlet air temperatures. All pressures in the cycle increase with increasing outlet air temperature. As outdoor air temperature increases, the compressor of an HTC tries to raise the refrigerant's saturation temperature in the condenser (condenser temperature) to facilitate effective heat transfer to the environment. The increase in the condenser temperature is directly proportional to the discharge pressure of the HTC. As shown in Figure 3a, the greatest increase in pressure is observed in the discharge pressure of HTC (P<sub>6</sub>). The increase in discharge pressure increases the pressure ratio of the HTC compressor, thereby increasing the suction pressure of the HTC (P<sub>6</sub>), as shown in Figure 3a. The discharge pressure of LTC (P<sub>2</sub>) is indirectly affected by changes in outlet air temperature. As the suction pressure of HTC increases, the evaporator temperature also increases. In the heat exchanger, the condenser temperature of LTC increases to provide the necessary heat transfer to the evaporator as the HTC evaporator temperature increases. The increase in the condenser temperature of LTC causes the discharge pressure of LTC (P<sub>2</sub>) to increase, as the condenser temperature of LTC is directly related to its discharge pressure (P<sub>2</sub>), as depicted in Figure 3b. The suction pressure of LTC (P<sub>1</sub>) is indirectly affected by changes in outlet air temperature. However, it is directly affected by changes in the evaporator temperature of the two-stage vapor-compression cascade refrigeration cycle (CRC). As the outlet air temperature increases, the evaporator temperature of CRC increases, thereby increasing the suction pressure of LTC (P<sub>1</sub>), as shown in Figure 3b. As the outlet air temperature changes from 28 °C to 43.5 °C, the percent increases in P<sub>6</sub>, P<sub>5</sub>, P<sub>2</sub>, and P<sub>1</sub> are 41.94%, 31.11%, 29.50%, and 17.50%, respectively.</p>
      <fig id="fig4">
        <label>Figure 4</label>
        <caption><p>Changes of mass flow rates of HTC and LTC as a function of outlet air temperature: (a) high temperature cycle (HTC); (b) low temperature cycle (LTC).</p></caption>
        <graphic xlink:href="obj/36/28/36286844bb6fe28068e590fee1cbf9423838f08b138035d8d043af955e6628d7"/>
      </fig>
      <p>Figure 4 depicts the variation of the mass flow rates of HTC and LTC with respect to the outlet air temperatures. The mass flow rates of HTC and LTC increase with increasing outlet air temperature. As outdoor air temperature increases, the compressor in HTC consumes more power than normal to reach the CRC condenser temperature and pressure. To provide extra power to the HTC, more refrigerant should be circulated through it. As the outdoor air temperature increases from 28 °C to 43.5 °C, the mass flow rate of the refrigerant flowing through HTC increases from 3.7 g/s to 4.3 g/s, as shown in Figure 4a. To maintain heat transfer balance in the heat exchanger, the refrigerant mass flow rate through LTC should also increase, as depicted in Figure 4b. The mass flow rate of LTC changes from 2.23 g/s to 2.38 g/s. When the percent increases in the mass flow rates are compared, the percent increases for HTC and LTC are 16.22% and 4.91%, respectively. The mass flow rate of refrigerant through HTC is much higher than that through LTC because HTC is directly affected by changes in outdoor air temperature, and the latent heat of vaporization of R-1234yf is lower than that of R-404a at the operating pressures in the experiments.</p>
      <fig id="fig5">
        <label>Figure 5</label>
        <caption><p>Changes of compressor power consumed by HTC and LTC as a function of outlet air temperature: (a) high temperature cycle (HTC); (b) low temperature cycle (LTC).</p></caption>
        <graphic xlink:href="obj/8b/cd/8bcd523e8c61a4aed7561ee1b55a1889314c6ac680f878a3f9c6a9ac31a40b5d"/>
      </fig>
      <p>Figure 5 shows the variation in power consumption of the compressors for HTC and LTC with respect to outside air temperature. R1234yf is used as a refrigerant in the HTC, and R404a is used as a refrigerant in LTC. As the outside air temperature ranges from 28 °C to 43.5 °C, the compressor power consumed in both cycles increases. When the temperature of the outside air passing through the condenser increases, the temperature difference between the condenser of the cascade system (also the condenser of the HTC) and the outside air (ambient air) will decrease, and since the condenser of the cascade system cannot release enough heat to the ambient air. To increase the condenser temperature for necessary heat transfer to the environment, the discharge pressure of the HTC will increase, and, as a natural consequence, the compressor power of the HTC will increase, as seen in Figure 5a. The pressure ratio of the HTC also increases as the compressor's power consumption increases. The increase in the pressure ratio of the HTC compressor increases its suction pressure, thereby increasing the discharge pressure of the LTC compressor and enabling effective heat exchange in the heat exchanger. As the discharge pressure of the LTC compressor increases, the compressor draws more power, as shown in Figure 5b. Another physical reason for the increase in the compressor power of HTC and LTC is the increase in the circulating mass flow rate of HTC and LTC. As the outside air temperature changes by 15.5 °C, the power of the compressors of HTC and LTC increases by 7.66 % and 6.03 %, respectively.</p>
      <fig id="fig6">
        <label>Figure 6</label>
        <caption><p>Change of capacity of the condenser of CRC as a function of outlet air temperature.</p></caption>
        <graphic xlink:href="obj/c7/79/c77918a26e95e99974310b6ddc32e143c92761712233095a675a9f71cc0c8659"/>
      </fig>
      <p>The variation in the capacity of the condenser in the two-stage vapor compression cascade refrigeration system (CRC) with respect to outside air temperature is shown in Figure 6. As the outside air temperature increases from 28 °C to 43.5 °C, the condenser temperature also increases from 47.62 °C to 63.11 °C. Two parameters affect the condenser capacity in CRC. These are the temperature difference between the condenser temperature and the outside air temperature, and the mass flow rate circulating through the HTC. The temperature difference between the condenser temperature and the outside air temperature is almost constant, around 19.5 °C, at outlet air temperatures between 28 °C and 43.5 °C, but the mass flow rate increases by 16–22% in these temperature ranges, as mentioned before. The most dominant factor affecting the condenser capacity of CRC is the refrigerant mass flow rate in HTC. As shown in Figure 6, the condenser capacity increases from 608.7 W to 624 W. The capacity of the condenser increases 0.987 W for every increase of 1 °C.</p>
      <fig id="fig7">
        <label>Figure 7</label>
        <caption><p>Change of capacity of the evaporator of CRC as a function of outlet air temperature.</p></caption>
        <graphic xlink:href="obj/fb/17/fb17ec18158cfb02b3ca570b1849bd0e3ec4f71bfa83b3004dd194ce4890923d"/>
      </fig>
      <p>Figure 7 shows the variation in the evaporator capacity of the CRC with respect to outside air temperature. As the outside air temperature increases from 28 °C to 43.5 °C, the temperature of the room to be refrigerated increases from −27 °C to −21 °C because the evaporator capacity of the CRC is insufficient to reduce the room temperature to the desired level. In other words, the evaporator capacity decreases as outside air temperature increases. The average decrease in evaporator capacity is around 1%. The evaporator of CRC is indirectly affected by changes in outdoor air temperature.</p>
      <fig id="fig8">
        <label>Figure 8</label>
        <caption><p>Change of coefficient of performance (COP) of CRC as a function of outlet air temperature.</p></caption>
        <graphic xlink:href="obj/ab/fc/abfc19082a6b1b0bfe762d2726283b25fb4c6371b1d2b57a16eed56f02cd9008"/>
      </fig>
      <p>The variation in the coefficient of performance (COP) of the two-stage vapor compression cascade refrigeration system (CRC) with respect to outdoor air temperature is shown in Figure 8. As the outdoor air temperature increases from 28 °C to 43.5 °C, the COP of CRC decreases. COP is mainly a function of the total power consumed by the compressors of HTC and LTC and the evaporator capacity of CRC. As outdoor air temperatures increase from 28 °C to 43.5 °C, the evaporator capacity decreases while the total power consumed by the compressors of HTC and LTC increases. As a result, the COP of CRC decreases, as shown in Figure 8. The COP of CRC decreases 7.23 % at the outdoor air temperatures between 28 °C and 43.5 °C.</p>
      <p>At higher outdoor air temperature, in order to prevent the coefficient of performance (COP) of the two-stage vapor compression cascade refrigeration system (CRC) from decreasing a certain value, the HTC compressor and cascade condenser with higher capacities should be selected to decrease the saturation pressure of the cascade condenser, variable speed fans for the condenser and inverter compressor for HTC should be employed to control the performance of two stage cascade refrigeration system, suitable environment friendly refrigeration couple having low discharge pressures at higher outdoor air temperature should be selected and intermediate temperature of the CRC should be optimized.</p>
    </sec>
    <sec id="sec6">
      <title>Conclusion</title>
      <p>The effects of outdoor air temperature on the energy parameters of the two-stage vapor-compression cascade refrigeration cycle (CRC), including the suction and discharge pressures of the compressors, the power consumed by the compressors, the mass flow rate, the evaporator capacity, the heat rejected by the condenser, and the COP were experimentally observed. The main conclusions drawn are as follows;</p>
      <list list-type="bullet">
        <list-item><p>At the increasing values of the outlet air temperatures between 28 °C and 43.5 °C, suction and discharge pressures of low temperature and high temperature cycle increased, the maximum increase in the pressure occurred at the discharge of the compressor of HTC as 41.94 %, while the minimum occurred at the suction of the compressor of LTC.</p></list-item>
        <list-item><p>The power consumption of the compressors in CRC increased with outdoor air temperature. The increase in power is 7.66% for the HTC compressor and 6.03% for the LTC compressor.</p></list-item>
        <list-item><p>The increase in outdoor air temperature also caused the mass flow rates of the refrigerants circulating through HTC and LTC to increase to meet the increased compressor power. The maximum increase in the mass flow rate occurred in HTC at 16.22 %, while the minimum occurred in LTC at 4.91 %.</p></list-item>
        <list-item><p>The heat rejection capacity of the condenser increased by 2.5%, while the evaporator capacity decreased by 1%, as the outlet air temperature increased from 28 °C to 43.5 °C.</p></list-item>
      </list>
    </sec>
  </body>
  <back>
    <ack><p>The authors would like to express our gratitude to TÜBİTAK for supporting our project titled &quot;Experimental Investigation of the Effect of Outside Air Temperature on a Two-Stage Vapor Compression Cascade Cooling System for a Current Refrigerant (Dış Hava Sıcaklığının İki Kademeli Buhar Sıkıştırmalı Kaskad Soğutma Sistemi Üzerine Etkisinin Güncel Bir Soğutucu Akışkan İçin Deneysel Olarak Araştırılması)&quot; (within the scope of the TÜBİTAK 2209/A University Students Research Projects Support Program.

The authors would also like to acknowledge the Scientific and Technological Research Council of Türkiye (TÜBİTAK-BİDEB) for their support under the '2224-A Grant Program for Participating in Scientific Activities Abroad (2026/1)' to present this paper at the 22nd International Conference on Sustainable Energy Technologies (SET2026), held in Kuala Lumpur, Malaysia, on August 13–15, 2026.</p></ack>
    <fn-group>
      <fn fn-type="con"><p>Ali Kilicarslan: Conceptualization, Methodology, Investigation, Formal analysis, Writing (original draft), Writing (review and editing), Supervision. Tahir Kaplan: Writing (original draft), Investigation.</p></fn>
      <fn fn-type="conflict"><p>The authors declare no competing interests.</p></fn>
      <fn fn-type="data-availability"><p>Not applicable. This study did not generate or analyse any datasets.</p></fn>
    </fn-group>
    <ref-list>
      <ref id="ref-7cad5ad0-bd41-4434-b478-34ff503016d6">
        <element-citation publication-type="journal">
          <person-group person-group-type="author">
            <string-name>Blanco Ojeda, Frank William Adolfo</string-name>
            <string-name>Almeida Queiroz, Marcus Vinícius</string-name>
            <string-name>Marcucci Pico, David Fernando</string-name>
            <string-name>dos Reis Parise, José Alberto</string-name>
            <string-name>Bandarra Filho, Enio Pedone</string-name>
          </person-group>
          <article-title>Experimental evaluation of low-GWP refrigerants R513A, R1234yf and R436A as alternatives for R134a in a cascade refrigeration cycle with R744</article-title>
          <source>International Journal of Refrigeration</source>
          <year>2022</year>
          <volume>144</volume>
          <page-range>175-187</page-range>
          <ext-link ext-link-type="uri" xlink:href="https://doi.org/10.1016/j.ijrefrig.2022.08.010">https://doi.org/10.1016/j.ijrefrig.2022.08.010</ext-link>
        </element-citation>
      </ref>
      <ref id="ref-7c09abd6-5a84-420e-9928-97d8673a1f51">
        <element-citation publication-type="journal">
          <person-group person-group-type="author">
            <string-name>Deymi-Dashtebayaz, Mahdi</string-name>
            <string-name>Sulin, Alexander</string-name>
            <string-name>Ryabova, Tatyana</string-name>
            <string-name>Sankina, Iuliia</string-name>
            <string-name>Farahnak, Mehdi</string-name>
            <string-name>Nazeri, Reza</string-name>
          </person-group>
          <article-title>Energy, exergoeconomic and environmental optimization of a cascade refrigeration system using different low GWP refrigerants</article-title>
          <source>Journal of Environmental Chemical Engineering</source>
          <year>2021</year>
          <volume>9</volume>
          <issue>6</issue>
          <page-range>106473</page-range>
          <ext-link ext-link-type="uri" xlink:href="https://doi.org/10.1016/j.jece.2021.106473">https://doi.org/10.1016/j.jece.2021.106473</ext-link>
        </element-citation>
      </ref>
      <ref id="ref-dbed100e-6e42-4346-ae88-2665966d1c32">
        <element-citation publication-type="journal">
          <person-group person-group-type="author">
            <string-name>Gupta</string-name>
            <string-name>V.K.</string-name>
          </person-group>
          <article-title>Numerical optimization of multi-stage cascaded refrigeration-heat pump system</article-title>
          <source>Journal of Heat Recovery Systems</source>
          <year>1985</year>
          <volume>5</volume>
          <issue>4</issue>
          <page-range>305-319</page-range>
          <publisher-name>Elsevier BV</publisher-name>
          <pub-id pub-id-type="doi">10.1016/0198-7593(85)90005-0</pub-id>
        </element-citation>
      </ref>
      <ref id="ref-0246feb1-908a-4176-9a3f-9a8e562b9ed6">
        <element-citation publication-type="book">
          <person-group person-group-type="author">
            <string-name>Holman</string-name>
            <string-name>J.P.</string-name>
          </person-group>
          <article-title>Experimental Methods for Engineers</article-title>
          <year>1984</year>
          <publisher-name>McGraw-Hill Book Company, USA</publisher-name>
        </element-citation>
      </ref>
      <ref id="ref-5eca1b1b-d9a4-4e27-9c14-457b50ff952b">
        <element-citation publication-type="journal">
          <person-group person-group-type="author">
            <string-name>Kilicarslan</string-name>
            <string-name>A.</string-name>
            <string-name>Hosoz</string-name>
            <string-name>M.</string-name>
          </person-group>
          <article-title>Energy and irreversibility analysis of a cascade refrigeration system for various refrigerant couples</article-title>
          <source>Energy Conversion and Management</source>
          <year>2010</year>
          <volume>51</volume>
          <issue>12</issue>
          <page-range>2947-2954</page-range>
          <publisher-name>Elsevier BV</publisher-name>
          <pub-id pub-id-type="doi">10.1016/j.enconman.2010.06.037</pub-id>
        </element-citation>
      </ref>
      <ref id="ref-6ae5a864-4fe8-41c7-bdad-7a42f4e680f4">
        <element-citation publication-type="webpage">
          <person-group person-group-type="author">
            <string-name>Klein</string-name>
            <string-name>S.A.</string-name>
          </person-group>
          <article-title>Engineering Equation Solver (EES) V10</article-title>
          <source>F-Chart Software, Madison, USA</source>
          <year>2020</year>
          <ext-link ext-link-type="uri" xlink:href="https://fchartsoftware.com">https://fchartsoftware.com</ext-link>
        </element-citation>
      </ref>
      <ref id="ref-8da7c994-5797-42b5-868c-e1f67cff30d3">
        <element-citation publication-type="journal">
          <person-group person-group-type="author">
            <string-name>Llopis, Rodrigo</string-name>
            <string-name>Sánchez, Daniel</string-name>
            <string-name>Sanz-Kock, Carlos</string-name>
            <string-name>Cabello, Ramón</string-name>
            <string-name>Torrella, Enrique</string-name>
          </person-group>
          <article-title>Energy and environmental comparison of two-stage solutions for commercial refrigeration at low temperature: Fluids and systems</article-title>
          <source>Applied Energy</source>
          <year>2015</year>
          <volume>138</volume>
          <page-range>133-142</page-range>
          <publisher-name>Elsevier BV</publisher-name>
          <pub-id pub-id-type="doi">10.1016/j.apenergy.2014.10.069</pub-id>
        </element-citation>
      </ref>
      <ref id="ref-d20687bd-b683-481e-9cc0-bd8c661ec86a">
        <element-citation publication-type="journal">
          <person-group person-group-type="author">
            <string-name>Sun, Zhili</string-name>
            <string-name>Wang, Qifan</string-name>
            <string-name>Xie, Zhiyuan</string-name>
            <string-name>Liu, Shengchun</string-name>
            <string-name>Su, Dandan</string-name>
            <string-name>Cui, Qi</string-name>
          </person-group>
          <article-title>Energy and exergy analysis of low GWP refrigerants in cascade refrigeration system</article-title>
          <source>Energy</source>
          <year>2019</year>
          <volume>170</volume>
          <page-range>1170-1180</page-range>
          <publisher-name>Elsevier BV</publisher-name>
          <pub-id pub-id-type="doi">10.1016/j.energy.2018.12.055</pub-id>
        </element-citation>
      </ref>
      <ref id="ref-e199f79b-928d-4ed7-a433-bd805eb54bf8">
        <element-citation publication-type="journal">
          <person-group person-group-type="author">
            <string-name>Sun, Zhili</string-name>
            <string-name>Wang, Yi’an</string-name>
          </person-group>
          <article-title>Comprehensive performance analysis of cascade refrigeration system with two-stage compression for industrial refrigeration</article-title>
          <source>Case Studies in Thermal Engineering</source>
          <year>2022</year>
          <volume>39</volume>
          <page-range>102400</page-range>
          <publisher-name>Elsevier BV</publisher-name>
          <pub-id pub-id-type="doi">10.1016/j.csite.2022.102400</pub-id>
        </element-citation>
      </ref>
      <ref id="ref-51d7d9c1-3ab6-4345-b8ad-f5a359ee87ea">
        <element-citation publication-type="journal">
          <person-group person-group-type="author">
            <string-name>Sun, Zhili</string-name>
            <string-name>Quan, Jianhua</string-name>
            <string-name>Wang, Yi’an</string-name>
            <string-name>Li, Ruishen</string-name>
            <string-name>Peng, Jie</string-name>
            <string-name>Zhang, Haoran</string-name>
            <string-name>Xu, Jiapei</string-name>
            <string-name>Sun, Huan</string-name>
            <string-name>Tian, Shen</string-name>
            <string-name>Dong, Shengming</string-name>
            <string-name>Hu, Kaiyong</string-name>
            <string-name>Chen, Wenxiang</string-name>
          </person-group>
          <article-title>Performance comparison of the single-refrigerant cascade refrigerating system</article-title>
          <source>Energy Reports</source>
          <year>2022</year>
          <volume>8</volume>
          <page-range>8259-8270</page-range>
          <publisher-name>Elsevier BV</publisher-name>
          <pub-id pub-id-type="doi">10.1016/j.egyr.2022.06.055</pub-id>
        </element-citation>
      </ref>
      <ref id="ref-3daee716-069b-475b-9502-2e1625a1319b">
        <element-citation publication-type="journal">
          <person-group person-group-type="author">
            <string-name>Udroiu, Cosmin-Mihai</string-name>
            <string-name>Mota-Babiloni, Adrián</string-name>
            <string-name>Navarro-Esbrí, Joaquín</string-name>
          </person-group>
          <article-title>Advanced two-stage cascade configurations for energy-efficient –80 °C refrigeration</article-title>
          <source>Energy Conversion and Management</source>
          <year>2022</year>
          <volume>267</volume>
          <page-range>115907</page-range>
          <publisher-name>Elsevier BV</publisher-name>
          <pub-id pub-id-type="doi">10.1016/j.enconman.2022.115907</pub-id>
        </element-citation>
      </ref>
      <ref id="ref-76137130-7020-4875-bff6-1d8b6ab30c92">
        <element-citation publication-type="webpage">
          <person-group person-group-type="author">
            <string-name>Wikipedia</string-name>
          </person-group>
          <article-title>List of refrigerants</article-title>
          <ext-link ext-link-type="uri" xlink:href="https://en.wikipedia.org/wiki/List_of_refrigerants">https://en.wikipedia.org/wiki/List_of_refrigerants</ext-link>
        </element-citation>
      </ref>
      <ref id="ref-08d80516-2205-44b5-ac4a-058232cab77b">
        <element-citation publication-type="journal">
          <person-group person-group-type="author">
            <string-name>Xu, Yixia</string-name>
            <string-name>Mickoleit, Erik</string-name>
            <string-name>Thomas, Christiane</string-name>
            <string-name>Jäger, Andreas</string-name>
            <string-name>Breitkopf, Cornelia</string-name>
            <string-name>Hesse, Ullrich</string-name>
          </person-group>
          <article-title>Experimental investigation of a novel cascade refrigeration system with a CO2 sublimation cycle as the lower stage</article-title>
          <source>International Journal of Refrigeration</source>
          <year>2021</year>
          <volume>131</volume>
          <page-range>938-946</page-range>
          <publisher-name>Elsevier BV</publisher-name>
          <pub-id pub-id-type="doi">10.1016/j.ijrefrig.2021.07.001</pub-id>
        </element-citation>
      </ref>
      <ref id="ref-5807403a-6aa1-46a2-8733-dcf30d2d59fe">
        <element-citation publication-type="journal">
          <person-group person-group-type="author">
            <string-name>Yılmaz</string-name>
            <string-name>B.</string-name>
            <string-name>Mançuhan</string-name>
            <string-name>E.</string-name>
            <string-name>Yılmaz</string-name>
            <string-name>D.</string-name>
          </person-group>
          <article-title>Theoretical analysis of a cascade refrigeration system with natural and synthetic working fluid pairs for ultra low temperature applications</article-title>
          <source>Journal of Thermal Science and Technology</source>
          <year>2020</year>
          <volume>40</volume>
          <issue>1</issue>
          <page-range>141-153</page-range>
        </element-citation>