Skip to content
Caravel Press

Conference paper

A two-stage refrigeration system for a supermarket using heat recovery and natural refrigerants

1The School of the Built Environment, The University of Nottingham, University Park, Nottingham, NG7 2RD, UK

Published
28 June 2004
Pages
1-5
Received
28 June 2004
DOI
10.65582/set.2004.035
Access
Open access, © 2004 Copyright WSSET
Download PDF5 pages · 125 KB

Abstract

The cooling demand of a supermarket is split into two systems operating at different temperature levels corresponding to low temperature frozen food, and high temperature chilled food storage. This paper describes a proposed system in which high temperature cooling is provided by a screw compressor driven by a gas engine, and low temperature cooling is provided by waste heat from the gas engine. A jet-pump refrigeration system is most suitable for driving the low temperature cooling system. A COP of 1.0 could be achieved for the jet-pump sub-cycle, which is high because the jet-pump discharges to an intermediate pressure. Secondary fluids transfer the coolth to the display cabinets so allowing the cooling plant to be housed in purpose built machine rooms, enabling hydrocarbon refrigerants to be used and minimising flammability risks.

Keywords. CHP; jet-pumps; ejectors; refrigeration; natural refrigerants

© 2004 Copyright WSSET

Free to read, download, print and share, unaltered and for non-commercial purposes, provided the authors, the paper and the proceedings are credited. Any other use, including commercial use or adaptation, needs written permission: write to [email protected].