Energy-conservation and Optimization Study of SPF Laboratory Animal Room Air System in Air Conditioning —Discussion on the Best Air Change Rates

, ,

1Design & Art school of Nanhua University, Hengyang, China

2Architecture resource & environment engineering school of Nanhua University, Hengyang, China

Published
23 September 2005
Pages
187-191
Received
23 September 2005
DOI
10.65582/set.2005.042
Access
Open access, © 2005 Copyright WSSET
Download PDF5 pages · 3.9 MB

Abstract

This paper simulated and analyzed the concrete project of laboratory animal room by CFD software, studies the best air change rate in laboratory room, and analyzed the energy-conservation potential of the air system of air conditioning. the studies indicated the best air changes of laboratory animal room is 14 times/h which take the air distribution of supplying in ceiling diffuser and exhausting air in underside. compare air change rates of 20 times/h which taken in old system, The 30% energy of the air system of the air conditioning can be saved.

Keywords. Energy-conservation; Laboratory Animal Room; the Best Air Change Rates