Skip to content
Caravel Press

Conference paper

The Contrast of the Absorption Refrigeration Cycle of the Water-Lithium Bromide-Lithium Nitrate and the Water-Lithium Bromide

, , ,

1Institute of energy and power engineering, North China Electric Power University, Baoding, China

Published
23 September 2005
Pages
342-345
Received
23 September 2005
DOI
10.65582/set.2005.077
Access
Open access, © 2005 Copyright WSSET
Download PDF4 pages · 3.4 MB

Abstract

The water-lithium bromide-lithium nitrate absorption refrigeration cycle is compared with the traditional water-lithium bromide system. The effect of temperature, which is generating temperature or condensing temperature or evaporating temperature, on system performance is analyzed. Moreover the double-effect absorption refrigeration system is also investigated. The results show that the COP of the water-lithium bromide-lithium nitrate absorption refrigeration system has been enhanced. And the other thermodynamics parameters are also improved. Especially for the double-effect absorption system, the COP has been increased by 30%,and then the f has been reduced by 12%. Thus, the water-lithium bromide-lithium nitrate absorption system has better performance than the system of water-lithium bromide.

Keywords. water-lithium Bromide-lithium nitrate; water-lithium Bromide; absorption refrigeration cycle; system performance

© 2005 Copyright WSSET

Free to read, download, print and share, unaltered and for non-commercial purposes, provided the authors, the paper and the proceedings are credited. Any other use, including commercial use or adaptation, needs written permission: write to [email protected].