Experimental Study of a Tube Based Indirect Evaporative Air Cooler

, ,

1Sokoto Energy Research Centre, Usmanu Danfodiyo University PMB2346, Sokoto, Nigeria

2Institute of Sustainable Energy Technologies, School of the Built Environment, University of Nottingham, United Kingdom

Published
31 August 2009
Pages
1-6
Received
31 August 2009
DOI
10.65582/set.2009.064
Access
Open access, © 2009 Copyright WSSET
Download PDF6 pages · 179 KB

Abstract

Horizontal concentric tubes evaporative cooler has been developed where the use of a pump to continuously wet the fibre evaporative cooling medium was eliminated. Initially 10 different paper-fibre samples were vertically supported in a tank containing water at the base. A suitable paper fibre was then selected for making the tubular evaporative cooling surfaces. The system operates as an indirect evaporative air cooler consisting of dry and wet air flow channels. Experimental results showed that up to 10°C temperature drop between the inlet and outlet of the product (dry channel) air was recorded. For an inlet relative humidity of 10%, the observed outlet values were 53.3% and 88.3% for the dry channel and the wet channel respectively. The dry channel serves as the product or supply air to the building space. In this paper, experimental results and relevant equations were used to evaluate the system effectiveness.

Keywords. Evaporative cooling; temperature; relative humidity; effectiveness

© 2009 Copyright WSSET

Free to read, download, print and share, unaltered and for non-commercial purposes, provided the authors, the paper and the proceedings are credited. Any other use, including commercial use or adaptation, needs written permission: write to [email protected].

← SET Proceedings