Actual Proof Test of Energy Conservation in Central Heating/Cooling System Adapting Surfactant Drag Reduction

, , ,

1Energy Technology Research Institute, National Institute of Advanced Industrial Science and Technology (AIST), 16-1, Onogawa, Tsukuba, 305-8569, Japan

2Department of Mechanical Engineering, Tokyo University of Science, Noda, Japan

3Shunan Regional Industry Promotion Center, Shunan, Japan

4Fujiwara Environmental Science Institute, Sapporo, Japan

Published
31 August 2009
Pages
1-4
Received
31 August 2009
DOI
10.65582/set.2009.068
Access
Open access, © 2009 Copyright WSSET
Download PDF4 pages · 231 KB

Abstract

Energy conservation test in central heating/cooling system using surfactant drag reduction was performed using the building of the Sapporo City Hall. It equips a pump with 37kW rated output for some 32tons of circulating water. LSP-01A was used as a surfactant and its concentration set at 0.4-0.5%. Reduction of energy consumption in the pump was measured by 65% in winter heating and by 47% in summer cooling. 52,000kW of electricity may be saved annually. Around 900days has passed after injection of surfactant, the system works successfully without problems of efficiency and rust.

Keywords. surfactant; drag reduction; central heating/cooling system