Skip to content
Caravel Press

Conference paper

The Experimental study of air source heat pump and floor heating in winter conditions

, ,

1University of Shanghai for science and technology, China, Shanghai

Published
24 August 2010
Pages
1-5
Received
24 August 2010
DOI
10.65582/set.2010.147
Access
Open access, © 2010 Copyright WSSET
Download PDF5 pages · 438 KB

Abstract

In hot summer and cold winter areas, air source heat pump is a good choice for heating and cooling. Combination of floor heating and air source heating pump is a promising solution for space heating in the middle of China. However, the air-source heat pump affected by the ambient air temperature and outlet water temperature and other factors. (1) Experimental testing of the air-source heat pump under various outdoor temperature was conducted; When the ambient temperature is -4°C with outlet water temperature near 55°C, the heat pump can operate normally and has the COP of 2.0. (2) The required floor heating supply water temperature under various outdoor temperatures is calculated, and the electricity consumption and average COP is calculated using BIN method for the whole heating season. The average seasonal COP is 3.41 for this case in Shanghai.

Keywords. air source heat pump; floor heating; Seasonal COP; BIN method

© 2010 Copyright WSSET

Free to read, download, print and share, unaltered and for non-commercial purposes, provided the authors, the paper and the proceedings are credited. Any other use, including commercial use or adaptation, needs written permission: write to [email protected].

← SET Proceedings