Experimental Investigation on an Ejector Cooling System

, ,

1Department of Built Environment, University of Nottingham, Nottingham, Ng7 2RD, United Kingdom

Published
2 September 2012
Pages
1083-1093
Received
2 September 2012
DOI
10.65582/set.2012.111
Access
Open access, © 2012 Copyright WSSET
Download PDF11 pages · 682 KB

Abstract

In order to analysis the feasibility and efficiency of a small scale steam ejector cooling system, a 0.5kW cooling capacity steam ejector system was constructed and tested under boiler temperature in the range 115°C to 130°C, and evaporator temperature in the range of 5°C to 10°C. System performances under different operating conditions including various boiler temperatures, evaporator temperatures and condenser pressures, were tested and reported. The effects of nozzle exit position on ejector performance were analyzed. Performance maps, useful for design and application were also presented. The results of both theoretical simulation and experimental study were compared and analyzed. The experimental data were found to be around 85% of the theoretical values.

Keywords. Ejector; cooling; water; experimental investigation