Skip to content
Caravel Press

Conference paper

Numerical Analysis of Heat Transfer Enhancement Performance of Pyramidal Longitudinal Vortex Generator

, ,

1School of Thermal Engineering, Shandong Jianzhu University, Jinan 250101, Shandong Province, China

Published
26 August 2013
Pages
225-229
Received
26 August 2013
DOI
10.65582/set.2013.020
Access
Open access, © 2013 Copyright WSSET
Download PDF5 pages · 432 KB

Abstract

Longitudinal Vortex Generators (LVG) is an effective passive heat transfer enhancement method. It is widely used because it’s simple and easy to implement. The authors had put forward a kind of triangular tapered LVG, triangular pyramidal LVG (TPLVG), to ehance heat dissipation of eletrical transformers. By numerical simulation, the influence of attack angle, and the height of the TPLVG had been analysed. The results showed that the TPLVGs increased the cooling capacity of the oil-immersed transformer heat sink, and the optimum attack angle and height is 45° and 10mm individually.The natural convection heat transfer coefficient is increased about 8.4%.

Keywords. (Oil-immersed transformer; longitudinal vortex generators; heat transfer enhancement; natural convection; numerical simulation)

© 2013 Copyright WSSET

Free to read, download, print and share, unaltered and for non-commercial purposes, provided the authors, the paper and the proceedings are credited. Any other use, including commercial use or adaptation, needs written permission: write to [email protected].