Performance Analysis on Water Heating System of a Sewage-source Heat Pump Applied in Public Bathroom

, , , ,

1College of Mechanical and Energy Engineering, Tongji University, 1239# Si Ping Road, Shanghai, China

2Shanghai Energy Company, 65# Chi Feng Road, Shanghai, China

Published
26 August 2013
Pages
1167-1171
Received
26 August 2013
DOI
10.65582/set.2013.126
Access
Open access, © 2013 Copyright WSSET
Download PDF5 pages · 106 KB

Abstract

With a heat pump system, the bath sewage water can be recycled to heat the bath water, which effectively saves energy used on the water heating. This study investigates the performance of the water heating system of a sewage-source heat pump used in a public bathroom of a university campus in Shanghai using on-site survey and TRNSYS simulation. It is found that the variation of both sewage temperature and flow rate can influence the system performance. A rise of 1℃ in sewage temperature results in an average increase of 0.03 in the coefficient of performance (COP) of the system and an average decrease of 0.11h in the system heating (namely, operational) time. The increase of sewage flow rate augments the system COP and lowers the system heating time in varied, but gradually decreased, magnitudes. Comparison of the effect of such two factors finds that the system performance is influenced by the sewage temperature more significantly. This study is expected to provide information for the design of water heating system of sewage-source heat pump in public bathrooms.

Keywords. water heating system; heat pump; TRNSYS; sewage temperature; sewage flow rate

© 2013 Copyright WSSET

Free to read, download, print and share, unaltered and for non-commercial purposes, provided the authors, the paper and the proceedings are credited. Any other use, including commercial use or adaptation, needs written permission: write to [email protected].

← SET Proceedings