Flow Properties of CO2 Hydrate Slurry Used as a Secondary Refrigerant

, , ,

1School of Energy and Power Engineering, University of Shanghai for Science and Technology, 516 Jungong Road, Shanghai 200093, China

Published
26 August 2013
Pages
1472-1478
Received
26 August 2013
DOI
10.65582/set.2013.159
Access
Open access, © 2013 Copyright WSSET
Download PDF7 pages · 437 KB

Abstract

An experimental loop was used to produce CO2 hydrate slurries by cooling after CO2 injection in precooled water. The flow characteristics of CO2 hydrate slurry for 8.2~23.1% volume fraction in 8mm straight stainless steel tubes were studied in a dynamic loop. The pressure drops of CO2 hydrate slurry were measured which shows increase with the increase of flow rate. The flow of CO2 hydrate slurry presents a non-Newtonian behavior. The flow transition of CO2 hydrate slurry was determined at 0.60 < v < 0.65m/s. At flow rate v < 0.60m/s, CO2 hydrate slurry behaves as a Herschel-Bulkley fluid. The apparent viscosity decreases with the increase of shear rate, which accords with its shear-thinning feature. At flow rate v > 0.65m/s, the apparent viscosity increases as the increase of shear rate which shows a shear-thickening feature. CO2 hydrate slurry behaves as a Dilatant fluid. The apparent viscosity of CO2 hydrate slurry changes from 8.5 to 10.6mPa·s at shearing rate γ̇=600s⁻¹. The rheological parameters and equations are determined which can provide the guideline for the research of CO2 hydrate slurry flow property and its application.

Keywords. Carbon dioxide; Hydrate slurry; Flow behavior; Pressure drop; Apparent viscosity

© 2013 Copyright WSSET

Free to read, download, print and share, unaltered and for non-commercial purposes, provided the authors, the paper and the proceedings are credited. Any other use, including commercial use or adaptation, needs written permission: write to [email protected].

← SET Proceedings