Field study on the operating characteristics of heat pump system with the flue gas heat recovery

, ,

1152, Gajeong-ro, Yuseong-gu, Deajeon, Korea

Published
26 August 2013
Pages
1606-1611
Received
26 August 2013
DOI
10.65582/set.2013.176
Access
Open access, © 2013 Copyright WSSET
Download PDF6 pages · 1.5 MB

Abstract

Effective reuse of waste heat is one of the most important research issues in the industrial field because large amount of the energy is exhausted as a form of mid-low temperature flue gas. Usually condensing heat recovery system which extracts both sensible and latent heat of the exhaust gas is used for this purpose. With heat pump, the recovered heat can be recycled to the high temperature industrial process because it can transfer heat energy of low temperature to high temperature. A 70 kW grade heat pump system with flue gas heat recovery was installed in KIER (Korea Institute of Energy Research). The system was connected to an absorption chiller-heater and used to heat return water to the absorption chiller-heater. The heat recovery system was used to transfer heat of the by-passed flue gas of the absorption chiller-heater to the low temperature side of the heat pump. Field study was performed during the winter season of 2012 and the operating characteristics of the heat pump system were analyzed. Based on the results of the field study, optimum operating temperature range was suggested, which was 51℃ of return water and 31℃ of source water. Finally the economic analysis was performed and about 50% of cost saving was expected.

Keywords. Heat pump; Condensing heat recovery; Flue gas; Heat recovery system

© 2013 Copyright WSSET

Free to read, download, print and share, unaltered and for non-commercial purposes, provided the authors, the paper and the proceedings are credited. Any other use, including commercial use or adaptation, needs written permission: write to [email protected].

← SET Proceedings