Thermal heterogeneity in indoor environment is not only critical for the thermal comfort with high indoor environment quality, but also contributes to the complexities of ZEB energy saving solutions. There is a growing consensus that variability in indoor conditions can be acceptable to occupants, reduce the energy consumption of buildings without compromising on the thermal comfort perception in occupied spaces. The contribution of this study is to create a novel indoor unit for the zoning air conditioning system and to reveal its thermal heterogeneity in an open-plan office in terms of temperature non-uniformities in the zoning thermal environment. The novel zoning air conditioning system is consisted of multiple supply air openings mounted on zone border separately and one central return air opening. Those supply air (SA) openings, central return air (RA) opening and indoor unit are connected by ducts, the return air is directly conditioned through the central RA and supplied to the border SA openings. Hence in each zone, circulating airflow form from border to the centre, which reduce the air convection between neighbouring zones and improve the thermal efficiency. In this study, the impact of various control strategies on zoning thermal environment are investigated by using computational fluid dynamics (CFD) numerical analysis which are validated through the full-scale field experiments. The CFD simulation prediction result is highly comparable to the experimental findings with an average temperature difference of approximately 0.4K. This research aims to investigate and evaluate the thermal heterogeneity of the novel zoning air conditioning system under varier control strategies. Cases studies under different operating schedules are successful in providing the acceptable temperature difference between neighbouring zones through the CFD numerical analysis. The mechanisms of zoning thermal heterogeneity for circulating airflow application are evaluated, the finding shows that the maximum temperature difference between the neighbouring zone can reach up to 2.8K.
Keywords. Zoning air conditioning system; CFD; field measurement; thermal heterogeneity; temperature non-uniformity
References
Japan’s Roadmap to “Beyond-Zero” Carbon. https://www.meti.go.jp/english/policy/energy_environment/global_warming/roadmap/
Shibuya T, Croxford B, 2016. The effect of climate change on office building energy consumption in Japan. Energy and Buildings. 117,1-11.
Ürge-Vorsatz D, Cabeza LF, Serrano S, Barreneche C, et al. 2015. Heating and cooling energy trends and drivers in buildings. Renewable and sustainable energy reviews, 41, 85-98.
Cao G, Awbi HB, Yao R, Fan YQ, et al. 2014. A review of the performance of different ventilation and airflow distribution systems in buildings. Building and environment, 73,171-186.
Fan YQ, Ito K, 2012. Energy consumption analysis intended for real office space with energy recovery ventilator by integrating BES and CFD approaches. Building and Environment, 52, 57-67.
Frontczak M and Wargocki P, 2011. Literature survey on how different factors influence human comfort in indoor environments. Building and Environment. 46, (4), 922-937.
Newsham G., Brand J., Donnelly C., Veitch J, et al. 2009. Linking indoor environment conditions to job satisfaction: a field study. Build Research and Information, 37 (2) 129-147.
Karimipanah T, Awbi HB, 2002. Theoretical and experimental investigation of impinging jet ventilation and comparison with wall displacement ventilation. Building and Environment 37(12),1329-1342.
Tian L, Lin Z, Wang Q, 2011. Experimental investigation of thermal and ventilation performances of stratum ventilation. Building Environment 46 (6),1309-1320.
Fan YQ, Toyashima M, Saito M, 2018. Energy conservation and thermal environment analysis of room air conditioner with intermittent supply airflow. International Journal of Low-Carbon Technologies.13 (1), 84-91.
Fan YQ. 2019.Performance evaluation of different air distraction system on thermal uniformity and energy saving: A Case study of a Japanese detached house. Indoor and Built Environment. 28 (2), 186-194.
Li H, Wang ZY, Li JC, Wang L, et al. 2022.Study on thermal comfort of interactive cascade ventilation based on body multi-node thermal demand. Energy and buildings, 273 (15),112404.
D. Al Assaad, K. Ghali, N. Ghaddar, 2018.Effectiveness of intermittent personalized ventilation assisting a chilled ceiling for enhanced thermal comfort and acceptable indoor air quality. Building and Environment. 144 (2), pp. 9-22.
Fan YQ. 2020. Mathematical and experimental analysis of the thermal effectiveness of an oscillating jet with side-to-side swing louvers in a cassette split type air conditioner. Indoor and Built Environment. 29(2), 240-254.
Zhang Z, Zhang W, Zhai ZJ, Chen Q, 2007.Evaluation of various turbulence models in predicting airflow and turbulence in enclosed environments by CFD: Part 2 —comparison with experimental data from literature. HVAC & R Research; 13(6):871-886.
Ito K, Inthavong K, Kurabuchi T, Ueda T, et al. 2015.CFD Benchmark Tests for Indoor Environmental Problems: Part 1 Isothermal/non-isothermal flow in 2D and 3D room model. International Journal of Architectural Engineering Technology. 2 (1), 01-22.
How to cite this article
Fan, Y., Hamada, M., Tamaki, S. and Wada, M. (2023). 'Experimental and numerical investigation on thermal heterogeneity of a novel zoning air conditioner'. SET Proceedings, 20(1), pp. 16-26. https://doi.org/10.65582/set.2023.003