Skip to content
Caravel Press

Conference paper

Simulation of thermal performance and thermal interference of horizontal slinky-loop ground heat exchangers

, ,

1Department of Architecture and Built Environment, the University of Nottingham, University Park, Nottingham, NG7 2RD, UK

Open access© 2023 The Author(s)Published 15 Aug 2023https://doi.org/10.65582/set.2023.030
Download PDF10 pages · 1.2 MB

Abstract

The thermal performance of a horizontal slinky ground heat exchanger has been investigated using a validated transient 3D model for different trench separations, initial soil temperature profiles and soil properties. The effect of trench separation on the thermal interference was analysed for a range of centre-to-centre distances between parallel trenches from 1.5 m to 11 m. The initial soil temperature was found to have a significant effect on the predicted thermal performance. The predicted heat extraction using a varying and more realistic initial soil temperature for a heating season would decrease with the increasing depth of installation whereas using a uniform initial temperature would lead to increasing heat extraction with installation depth. It has also been found that soil with a high thermal conductivity would exacerbate the thermal interference between trenches with a small separation as a results of heat depletion in the ground.

Keywords. Ground source heat pump; Horizontal slinky-loop heat exchanger; Thermal interference; Trench separation

How to cite this article

Luo, M., Gan, G. and Lin, L. (2023). 'Simulation of thermal performance and thermal interference of horizontal slinky-loop ground heat exchangers'. SET Proceedings, 20(1), pp. 281-290. https://doi.org/10.65582/set.2023.030

© 2023 The Author(s)

Published by Caravel Press on behalf of WSSET. Free to read and download. For any other use, please contact the authors.

← SET Proceedings