Oil compatibility study of R466A for replacing R410A by using compressor test loops

, , , , , , , , , ,

1Korea Institute of Energy Research, Gajeong-ro 152, Yuseong-gu, Daejeon

Published
12 December 2024
Pages
71-76
Received
12 December 2024
DOI
10.65582/set.2024.009
Access
Open access, © 2024 Copyright University of Nottingham & WSSET
Download PDF6 pages · 2.0 MB

Abstract

To reduce the direct emissions from the building sector caused by the utilization of fossil fuels, electrification of heating has been considered the main strategy for achieving net-zero emissions. Among many heat pump systems, VRF systems have been widely used in commercial buildings. However, VRF systems have a large amount of refrigerant inventory. Therefore, a non-hazardous and low-GWP refrigerant to replace R410A should be dropped in existing R410A-based VRF systems. For the drop-in, compatibility between a new refrigerant and existing oil is the key factor. In this study, R466A was dropped in the R410A compressor test loops to confirm the compatibility. As a result, compressor test loops operated for 500 hours without any problem.

Keywords. Low-GWP; R466A; VRF Systems; Oil Compatibility