Most buildings are constructed with concrete. The thermal capacity of such elements in buildings provides the possibility to store thermal energy. In this study, the character of cold storage based on building envelope was explored. The TRNSYS model was set up based on an actual office building with a floor radiant cooling system, which normally opens during 8:00-18:00 on workdays. The local peak period for electricity is 16:00-22:00, the valley tariff period is 2:00-8:00, and the parity period is 8:00-16:00 during cooling. Based on the peak-valley electricity price, four operating strategies of cold storage were proposed, namely, condition 1 (2:00-8:00), condition 2 (2:00-10:00), condition 3 (2:00-12:00), and condition 4(2:00-14:00). The simulation showed that under the cold thermal storage conditions, the indoor air temperature was lower in the morning and kept increasing during working time, which led to temperature drift in the office room. For condition 1 and 2, the indoor thermal comfort cannot be assured as indoor temperature can be higher than the comfort level in later afternoon. For condition 3 and 4, the thermal comfort was better, and the PMV index can be kept in the range of -1 to 1 all the time. Results of thermal balance showed that the cold can be stored both in the cooling floor and internal walls by reduced the structure temperature, and the cooling loss during night was less than 10%. The running cost of both condition 3 and 4 were lower than the normal condition. Condition 3 (with same running time of the normal condition) had better economic effect, in which running cost was reduced by 16.2%. The results provided information for the cost saving operation of radiant cooling systems based on building envelope cold storage.
Li, J. (2024) ‘Comparison of the environmental, energy, and thermal comfort performance of air and radiant cooling systems in a zero-energy office building in Singapore’, Energy and Buildings, 318, pp. 114487.
Olesen, B. (2004) ‘Operation and control of activated slab heating and cooling systems’, CIB World Building Congress. Canada.
Qi, Y. (2015) ‘The character of cooling-supply researching of the cooling system directly linked by buried pipes’, Shandong Jianzhu University. (in Chinese)
Rong, G. (2020) ‘Discussion on building entity energy storage’, Building Energy and Environment, 39(1), pp. 84-87. (in Chinese)
Zhang, F. (2021) ‘A critical review of the research about radiant cooling systems in China’, Energy and Buildings, 235, pp. 110756.
Zhang, L. (2016) ‘Performance analysis of thermal storage characteristic for the building envelope in a radiant floor cooling system’, Journal of Shandong Jianzhu University, 31(6), pp. 576-582. (in Chinese)
Zhang, L. (2019) ‘Research on control strategy of radiant floor cooling system in office buildings’, Shandong Jianzhu University. (in Chinese)
Zhang, L. (2020) ‘A two-dimensional numerical analysis for thermal performance of an Intermittently operated radiant floor heating system in a transient external climatic condition’, Heat Transfer Engineering, 41(9-10), pp. 825-839.
Zhou, L. (2020) ‘Study on thermal and energy-saving performances of pipe-embedded wall utilizing low-grade energy’, Applied Thermal Engineering, 176, pp. 115477.
How to cite this article
Wang, H., Yan, R., Cui, Z., Sun, J., Meng, H. and Lin, H. (2024). 'Study on effect of operating time for thermal storage based on building envelope'. SET Proceedings, 21(3), pp. 209-218. https://doi.org/10.65582/set.2024.126