A new evaporative condensation refrigerant pump heat pipe air-conditioning unit based on a microchannel heat pipe heat exchanger is proposed. Performance experiments are conducted of the unit, and the experimental results show that the cooling capacity of the unit in the dry, wet, and mixed modes can reach 112.1, 105.8, and 115.4 kW, respectively, the optimal airflow ratio of the secondary/primary airflow is 2.2, 1.8, and 1.8, respectively, and the EER decreases with increasing airflow ratio. With increasing dry- and wet-bulb temperatures of the secondary-side inlet air, the cooling capacity and energy efficiency ratio of the unit decrease, and the energy efficiency ratio in the wet mode is higher than that in the dry mode, which can prolong the operating hours of the wet mode within the operating temperature range of the dry mode and improve the energy efficiency of the unit. A new calculation method for the refrigerant charge is proposed, and the optimal refrigerant charge is 32 kg based on the experimental results, which agrees with the theoretical calculation results
Insight 2021: Competitive Landscape and Market Share of China's Data Center Industry [J]. Data center construction+ 2021(8):4.
Jiang L, Yong T, Wei Z, et al. Design and fabrication of sintered wick for miniature cylindrical heat pipe[J]. Transactions of Nonferrous Metals Society of China, 2014, 24(1): 292-301.
Liu C,Chen Y,Feng D,et al. Experimental study on temperature uniformity and heat transfer performance of nitrogen loop heat pipe with large area and multi-heat source[J]. Applied thermal engineering: Design,processes,equipment, economics,2022(210-):210.
Ma G Y,Wei C C,Zhang S,et al. Application of a pumped loop heat pipe heat exchanger unit for a small data center[J]. Beijing Gongye Daxue Xuebao / Journal of Beijing University of Technology,2015,41(3):439-445.
A J D,A Y L,B S D,et al. Experimental investigation of an integrated cooling system driven by both liquid refrigerant pump and vapor compressor[J]. Energy and Buildings,2017,154:560-568.
Yan G, Feng Y, Peng L. Experimental analysis of a novel cooling system driven by liquid refrigerant pump and vapor compressor[J]. International Journal of Refrigeration, 2015, 49: 11-18.
Shuailing L, Guoyuan M, Xiaoya J, et al. Performance of a mechanically-driven loop heat pipe heat recovery system[J]. Applied Thermal Engineering, 2022, 207: 118066.
Chen F, Zhou X, Liao S. Energy Saving Model and Calculation Example of Three Cooling Schemes for Data Center in Hot Summer and Cold Winter Area[J]. Journal of Power and Energy Engineering, 2022, 9(12): 1-20.
Shuailing L,Guoyuan M,Xiaoya J,et al. Performance of a mechanically-driven loop heat pipe heat recovery system[J].Applied thermal engineering: Design, processes,equipment,economics,2022(207-):207.
Ohadi M M,Dessiatoun S V,Choo K,et al. A comparison analysis of air,liquid, and two-phase cooling of data centers[C]// 2012:58-63.
Wei A,Ren X,Lin S,et al. CFD analysis on flow and heat transfer mechanism of a microchannel Ω-shape heat pipe under zero gravity condition[J].International Journal of Heat and Mass Transfer,2020,163:120448.
Han Z , Xue D , Wei H , et al. Study on operation strategy of evaporative cooling composite air-conditioning system in data center[J]. Renewable Energy, 2021, 177.
Yue zheng M , Shu xue X , Guo yuan M ,et al. Characteristic Analysis and Experimental Study on a Hybrid System with Magnetic Pump-driven Two Phase Cooling System[J].Journal of Refrigeration, 2016,37(03):1-5.
Lin Yucong, Liu Jinping, Xu Xiongwen ,et al. Experimental Research on Air Conditioning System of a Computer Room Based on Refrigerant Pump Pressurization[J].Journal of Refrigeration, 2020,41(05):83-88.
Xue Lianzheng, Ma Guoyuan, Zhou Feng, et al. Performance Analysis of Gas-Pump-Driven Free-cooling Unit in a Small Data Center[J].Journal of Refrigeration, 2019,40(04):1-9.
Bai Kaiyang, Ma Guoyuan, Zhou Feng , et al. Performance characteristics of pump-driven mechanical refrigeration and thermosyphon integrated system[J]. Heating Ventilating & Air Conditioning,2016,46(09):109-115.
Liu Zhenyu, Huang Xiang, Chang Jianpei , et al. Design and test analysis of evaporative cooling(condensation) air conditioning unit data center [J]. Refrigeration and Air-conditioning, 2020, 20(1):6. (in Chinese)
GB 50174-2017. Code for design of data centers [S].Beijing: China planning press,2017.(in Chinese)
T/DZJN 27—2021. Evaporative cooling air - conditioning equipment of data centers [S]. Beijing:China planning press, 2021. (in Chinese)
Wang Wen , Xiong Rui, Tu Chuan-jing.Analysis of the Filling Quantity for Separated Type Heat Pipe.Power Engineering ,1997(03):67-69+73. (in Chinese)
Zhang Hong. Inverstigation on the optimized working status of separated type heat pipe heat exchangers [J]. Petrochemical Equipment Technology,1996(03):13-17+65. (in Chinese)
How to cite this article
Chu, J., Huang, X., Chu, H., Yang, L., Wang, Y., Tang, X. and Tian, J. (2024). 'Experimental study of an evaporative condensation refrigerant pump heat pipe air-conditioning unit based on a microchannel heat exchanger'. SET Proceedings, 21(4), pp. 414-428. https://doi.org/10.65582/set.2024.203