A Study on performance of heat pump using domestic supply water source and geothermal source

, ,

1Institute of Technology & Quality Development, Hyundai Engineering & Construction Co., Ltd, Seoul, Republic of Korea

Published
24 August 2010
Pages
1-5
Received
24 August 2010
DOI
10.65582/set.2010.022
Access
Open access, © 2010 Copyright WSSET
Download PDF5 pages · 1.2 MB

Abstract

This paper is to make it possible to check geothermal heat-pump performance by using building running water heat-source, a energy we never make use of. To check heat-pump performance, geothermal heat-pump 3RT, heat exchanger 100 m (¢12mm of PE) in water tank, and Vertical heat exchanger 100m (¢32mm of HDPE) were set up in Mock-up House. In fact, heatpump 3RT needs vertical heat exchanger 150m. The experimental results are that in winter season around 0.67RT was taken off from water tank and the rest 2.23 RT was from vertical heat exchanger while using domestic water (710 liter/day, based on 4 people) from water tank During the time of checking, geothermal heat-pump COP was at 4.2, which is enough to meet the standard of national geothermal heat-pump COP, 3.45. It depends on the amount of water supply, but It can be reduced to about 50m of vertical heat exchanger in Residential building so that you can save 20% of the total construction cost. In the future, the study on how to make optimal design in accordance with heat exchanger quality and shape in water tank.

Keywords. Geothermal Heat Pump; Water Storage Tank; Borehole Heat Exchanger; Municipal Waste Water

© 2010 Copyright WSSET

Free to read, download, print and share, unaltered and for non-commercial purposes, provided the authors, the paper and the proceedings are credited. Any other use, including commercial use or adaptation, needs written permission: write to [email protected].

← SET Proceedings