Skip to content
Caravel Press

Conference paper

Numerical comparison between two advanced HGHEs

,

1Department of Architetture, Università di Ferrara, Italy

2DICAM, Università di Bologna, Italy

Published
4 September 2011
Pages
1-6
Received
4 September 2011
DOI
10.65582/set.2011.069
Access
Open access, © 2011 Copyright WSSET
Download PDF6 pages · 1.5 MB

Abstract

Several solutions are currently being tested to improve the thermal efficiency of ground heat exchangers (GHEs) employed in ground source heat pumps. For shallow exchangers, the main effort is towards maximizing the surface available for heat exchange, while reducing the interference among exchangers; popular solutions towards this end are the slinky coil and the radiator shape. Recently, the flat panel has been proposed as novel alternative for horizontal exchangers. In this paper, the performance and impact of the radiator and flat panel installations are compared by solving the transient flow and heat transport problem within the surrounding ground via a numerical model. Adopting the same computational domain, boundary and initial conditions (the latter derived via a preliminary model run in absence of the GHE), and identical specific power outputs, the two installations yield different resulting domain thermal fields. The flat panel showed a higher capability to affect larger volumes of surrounding ground, so the soil temperatures reached values less extreme than in the radiator case. Since the temperatures remain 2÷3 degrees warmer, a higher COP is expected for the flat panel.

Keywords. ground heat exchangers; radiator; flat panel; numerical comparison

© 2011 Copyright WSSET

Free to read, download, print and share, unaltered and for non-commercial purposes, provided the authors, the paper and the proceedings are credited. Any other use, including commercial use or adaptation, needs written permission: write to [email protected].

← SET Proceedings