Numerical study of novel corrugated heat and moisture exchanging sheets applied to counter-flow dew point air cooler

, , , , ,

1School of Engineering, University of Hull, UK, HU6 7RX

2Beijing Key Lab of Heating, Gas Supply, Ventilating and Air Conditioning Engineering, Beijing University of Civil Engineering and Architecture, Beijing University of Civil Engineering and Architecture, Beijing, China, 100044

Published
6 July 2016
Pages
96-106
Received
6 July 2016
DOI
10.65582/set.2015.098
Access
Open access, © 2015 Copyright WSSET
Download PDF11 pages · 1.3 MB

Abstract

The authors present a numerical investigation on the performance of corrugated-sheets-stacked heat and moisture exchanger (HMX) applied to counter-flow dew point air cooler. The computational simulation software for this investigation was developed under Engineering Equation Solver (EES) environment. The results showed that the HMX could run with stably high effectiveness (generally, wet bulb effectiveness over 130% and dew point effectiveness over 85%) and supply product air at stably low temperature, as well as improve automatically the total cooling capacity with the temperature rise of the ambient air. The HMX also presented high adaptability to the various climate conditions in Southern Europe, Northern Europe and the UK. The renovation in heat exchanger configuration could lead to significant increase in the cooling capacity and COP for dew point coolers, and decrease in size and cost of the coolers at the same cooling output. The major factor affecting the cooling performance was the relative humidity of inlet air, therefore the HMX was particularly suitable for heat-intensive places in winter, i.e. computer data centres. The optimized air-channel’s geometric sizes of height and length were 0.005m and 1.0m respectively. The ideal range of operational conditions of working air ratio should be between 0.3 and 0.5 and the reasonable velocity of inlet air around 1m/s, while the inlet water temperature had little effect on the performance.

Keywords. Dew point cooling; Corrugated sheet; Heat and moisture exchanger; Counter-flow; Simulation