Parametric Characterisation and Operating Boundaries of Air- and Liquid-Cooling Architectures in High-Density Data Centres

, , , , ,

1Tsinghua University, Beijing, China

Open accessCC BY 4.0Published 23 Nov 2026https://doi.org/10.65582/set.2026.022
Download PDF13 pages · 2.2 MB

Abstract

The rapid growth of artificial intelligence has continuously increased chip and rack power densities, making thermal management an increasingly important factor in both the cooling capability and energy efficiency of data centres. Improving heat transfer efficiency can reduce the temperature difference required for heat rejection and potentially decrease the dependence on energy-intensive mechanical cooling. However, comparisons among air cooling, cold-plate cooling, and immersion cooling are often affected by simultaneous differences in coolant properties, package structures, heat-sink dimensions, and cooling-source temperatures. In this study, a unified chip-to-facility thermal resistance framework was developed to compare rack-level air cooling, single-phase lidded cold-plate cooling, single-phase Direct-to-Die cold-plate cooling, and single-phase immersion cooling. Under unified geometric conditions with a common fin height of 20 mm, the total thermal resistance of the liquid-cooling architectures was only 24.2%–37.5% of that of air cooling. The dominant thermal resistance also shifted substantially among different architectures. Air cooling was mainly limited by the heat sink, heat exchanger, and airflow warming and mixing processes, whereas thermal interface materials and heat spreading within the base plate became increasingly important for liquid cooling. Architecture-specific enhancement strategies were therefore introduced by improving thermal interface materials, heat-spreading structures, and heat-sink dimensions. At the adopted coolant-velocity modelling upper bounds and a facility-water inlet temperature of 10 °C, the second-generation configurations achieved maximum single-chip cooling capacities of 1.74, 4.43, 6.09, and 6.34 kW for air cooling, lidded cold-plate cooling, Direct-to-Die cold-plate cooling, and immersion cooling, respectively. The results demonstrated that different cooling architectures required different enhancement pathways. Reducing thermal resistance not only increased the achievable cooling capacity but also provided greater flexibility for integrating free-cooling sources and reducing reliance on mechanical refrigeration, supporting the development of more sustainable high-density data centres.

Keywords. Data centre cooling; Thermal resistance analysis; Liquid cooling; Cooling architectures; Heat dissipation capability

© 2026 The Author(s). Published by Caravel Press.

Anyone may read, download, copy, distribute and build on this article, in any medium or format, provided the authors and the original article are credited. Read the CC BY 4.0 licence

← SET Proceedings