Operational Performance of a Water-Source Variable Refrigerant Flow System Coupled with a Dual-Season Cooling Tower in Actual Operation

, , , ,

1Chongqing University, Chongqing, China

2Sultan Qaboos University, Muscat, Oman

3PowerChina Hubei Engineering Co., Ltd, Wuhan, China

Open accessCC BY 4.0Published 23 Nov 2026https://doi.org/10.65582/set.2026.023
Download PDF14 pages · 1.8 MB

Abstract

To investigate the suitability and operational characteristics of a water-source variable refrigerant flow (WSVRF) system coupled with a dual-season cooling tower in regions with hot summers and cold winters, a small-scale test platform was established in an office building in Chongqing, China. Field experiments were conducted under representative summer cooling and winter heating conditions. On the basis of field-measured data, this study analysed the changing rules of circulating water temperature, WSVRF operational performance, and overall system coefficient of performance (COP) with variable outdoor meteorological parameters and operating loads. Seasonal differences in system behaviour were also evaluated. Results showed that, under summer wet-bulb temperatures (Twb) of 25.0–28.8 °C, the cooling tower effectively satisfied the system’s heat rejection requirement and maintained stable circulating water temperatures. The system COP ranged from 3.46 to 4.29. Under winter Twb of 11.9–13.6 °C, COP ranged from 2.90 to 4.09, while the cooling tower operated stably with water as the circulating medium and exhibited good performance under partial-load conditions. When the outdoor Twb fell below 8.65 °C, the cooling capacity of the cooling tower declined markedly. The circulating water temperature approached the lower operational limit of 5 °C for the WSVRF system, resulting in unstable operation and failure to sustain normal performance. This threshold therefore marked the minimum operating limit for reliable winter performance with the given configuration. The results presented herein enable quantification of the operating range for WSVRF systems integrated with dual-season cooling towers, and offer a benchmark to assess the feasibility of deploying such systems in regions featuring hot summers and cold winters.

Keywords. Water-source variable refrigerant flow system; Dual-season cooling tower; Field experiment; Coefficient of performance

© 2026 The Author(s). Published by Caravel Press.

Anyone may read, download, copy, distribute and build on this article, in any medium or format, provided the authors and the original article are credited. Read the CC BY 4.0 licence

← SET Proceedings