Skip to content
Caravel Press

Conference paper

Experimental Study on Temperature Distribution of Two-Stage Cascade Vapor-Compression Cycle

, , ,

1Graduate School, Department of Mechanical and Precision Engineering, Gyeongsang National University, 445 Impyeong-dong, Gyeongsang-namdo 650-160, Korea

2School of Mechanical and Aerospace Engineering, the Institute of Marine Industry, Gyeongsang National University, 445 Impyeong-dong, Gyeongsang-namdo 650-160, Korea

Published
23 September 2005
Pages
526-531
Received
23 September 2005
DOI
10.65582/set.2005.117
Access
Open access, © 2005 Copyright WSSET
Download PDF6 pages · 5.5 MB

Abstract

This paper presents the experimental study on temperature distribution of two-stage cascade vapor-compression system for achieving super-low temperature. On this study, two different types of Halocarbon refrigerants are utilized, HCFC-22 and HFC-23. Four successive trials were conducted for different outlet pressure of low stage compressor. By changing mass of refrigerant, low-stage compressor outlet is adjusted from 6 bar to 21 bar. The lowest temperature achieved by this arrangement is down to -85°C at 16 bar of low stage compressor outlet. It is also found that at the range of 6 to 16 bars, evaporation temperature decrease as compressor outlet-pressure increase.

Keywords. Cascade vapor-compression; high stage; low-stage

© 2005 Copyright WSSET

Free to read, download, print and share, unaltered and for non-commercial purposes, provided the authors, the paper and the proceedings are credited. Any other use, including commercial use or adaptation, needs written permission: write to [email protected].