Experiments on the long-term behavior of practical U-shaped ground coupled heat exchangers (GCHE) were carried out. Based on the grey theory, GM(1,1) model was established, and further topological prediction was given for key parameters including heat-exchange rate Q and the coefficient of heat transfer K. Simulated results showed that there is a better coincidence between the test and predicted data. During the long-term operation of the GCHE, due to the unbalance of the load heat transfer is likely to become worse and worse, especially in the summer. The summer mode can be divided into three working zones: transitional period, steady period and weakening period. A dimensionless runtime τ is presented to express the long-term behavior of K, where K = aτ^b. The runtime τ of three working zones is determined as 0-25%, 25-80% and 80-100%, respectively. Prey prediction can provide us with a quantitative basis for stable operation and next optimization of the ground source heat pump system (GSHP).
Bose, J. E. 1993. Today’s ground source heat pump. Energy Engineering. Vol 90. No5. p26-39. USA.
Yian GuU, D. L. Oneal.1998.Modeling the effect of backfills on U-tube ground coil performance. ASHRAE Trans. Vol104. No2. p356-364. USA.
B.Sanner, W. Burkhard.2003.Current status of ground source heat pumps and underground thermal energy storage in Europe. Geothermics. Vol32. No7. p579-588. UK.
Dai, C.,Zhang, Q. 1995. Shape downhole heat exchanger in conductive temperature gradient field. Acta Energiae Solaris Sinica. Vol16. No3. p247-252. China.
Zhao, J., Dai, C.& Liu, Q. 2000. Similarity solutions for downhole coaxial heat exchangers in porous medium. Acta Energiae Solaris Sinica. Vol21. No3. p272-252. China.
Carol Gauthier, Marcel Lacroix & Herver Bernier. 1997. Numerical simulation of soil heat exchanger-storage systems for greenhouses. Solar Energy. Vol60. No6. p333-346. USA.
Chiasson, A.C., S.J. Rees & J.D. Spitler. 2000. A preliminary assessment of the effects of ground -water flow on closed-loop ground-source heat pump systems, ASHRAE Transactions. Vol106. No1. 380-393. USA.
Xinguo Li, Jun Zhao & Qian Zhou. 2005. Inner heat source model with heat and moisture transfer in soil around the underground heat exchanger. Applied Thermal Engineering. Vol25. No8. p1565-1577. UK.
Julong Deng.Grey system theory. 1990. HUST Publishing Company. Wuhan. China.
Reuss, M.Beck & J.P.Muller. 1997. Design of a Seasonal Thermal Energy Storage in the Ground. Solar Energy. Vol59. No12. p247-257. USA.
How to cite this article
Wang, H., Zhao, J., Song, Z. and Li, X. (2005). 'Experimental Research and Grey Prediction on the Long-term Behavior of U-shaped Ground Coupled Heat Exchangers'. SET Proceedings, 4(1), pp. 543-547. https://doi.org/10.65582/set.2005.120