Skip to content
Caravel Press

Conference paper

Parametric thermodynamic analysis for single and double effect absorption systems

, , ,

1Arab Academy for science, Technology and Maritime Transport P.O. Box 1029 Abo Qir, Alexandria, Egypt

Published
4 September 2011
Pages
1-6
Received
4 September 2011
DOI
10.65582/set.2011.266
Access
Open access, © 2011 Copyright WSSET
Download PDF6 pages · 375 KB

Abstract

Absorption refrigeration system presents a promising alternative for vapor compression system due to the increase of the environmental problems and electricity cost .In recent years, research has been increased to improve the performance of the absorption systems A parametric thermodynamic analysis is developed for both single and double effect absorption systems in order study the effect of different operational parameters on system performance as represented by the COP in order to determine which component has the greater effect on the performance of the system. The results showed that the maximum COP is achieved at higher evaporator and generator temperatures and lower absorber and condenser temperatures. The results also showed that the absorber is the most effective component in the systems as it has a significant effect on the performance of the system for both single and double effect systems and should be regarded as a system component that needs improvement.

Keywords. Absorption system; Energy; Generator; COP; Absorber

© 2011 Copyright WSSET

Free to read, download, print and share, unaltered and for non-commercial purposes, provided the authors, the paper and the proceedings are credited. Any other use, including commercial use or adaptation, needs written permission: write to [email protected].

← SET Proceedings